Technical Data
OPERATING VOLTAGE: 230V 50Hz (UK & Europe)
CAPACITY: Digital DSI - 4 ballasts max
DALI - 1 ballast max
COLOUR: White bezel
MATERIAL: Flame retardant PC/ABS
WEIGHT: 50g
IP RATING: 4X
OPERATING TEMPERATURE: 0 C to 55 C
Mid-Bay:
MOUNTING HEIGHT: 12.0m max
RANGE: Cone-shaped detection pattern,
diameter at floor level (d) = 1.75 x mounting height (h)
d
Important Additional Notes
1.
A means for disconnection must be incorporated in the fixed wiring in accordance with the current wiring regulations.
2.
Although nominally 12V, the dimming output is not SELV and therefore should be treated with the same respect as mains
with regard to wiring practice. The 0V line of the dimming output is almost at Neutral potential.
3.
The dimming control output should be connected only to the control input of the ballasts - never to other detectors.
4.
This equipment should be used to control only those ballasts powered from the same phase as the detector.
5.
Due to the fact that the photocell is on the ceiling looking down, it is not possible for measurements made with a lux meter on
the working plane to remain constant when daylight illuminates the ceiling and the working plane to a differing extent.
Therefore, products of this type should be regarded as capable of maintaining an APPROXIMATE light level only.
6.
In order to achieve satisfactory light level regulating operation, a detector must observe a substantially greater portion of
artificial light from the luminaire(s) under its control than from neighbouring luminaires not under its control. This is particularly
important when planning the installed layout of linear luminaires that have an integral detector positioned at one end.
7.
The recommended position for the sensor is in the middle of the luminaire. Where this is not possible and the sensor is fitted
near one end of the lamps, please ensure that the sensor is at the "cold" end of the lamps.
8.
This equipment switches lights no more frequently than would a responsible human occupant. However, manufacturers of
some particular lighting types (e.g. '2D' luminaires) may specify a maximum number of switching cycles in order to achieve a
predicted lamp life. Please check with the manufacturer of the luminaires to ensure that they are compatible with automatic
controls in this respect.
Ex-Or
Novar ED&S LImited
Haydock Lane, Haydock, Merseyside WA11 9UJ
Tel: +44 (0)1942 719229
Fax: +44 (0)1942 508753
Email: technicalsales.ex-or@honeywell.com
www.ex-or.com
o
o
h
Hi-Bay:
MOUNTING HEIGHT: 16.0m max
RANGE: Cone-shaped detection pattern,
diameter at floor level (d) = 1 x mounting height (h)
d
At the end of their useful life
the packaging and product
should be disposed of via a
suitable recycling centre.
Do not dispose of with normal
household waste.
Do not burn.
h
W5099B

Advertisement

loading

This manual is also suitable for:

Ex-or mid-bay ms1200dalimbwEx-or hi-bay ms1200dihbwEx-or hi-bay ms1200dalihbw