Marine type container refrigeration unit (82 pages)
Summary of Contents for Daikin LXE10E-1
Page 1
Marine type Container Refrigeration Unit Service Manual DAIKIN CONTAINER LXE10E-1 TR 03-06...
Page 2
Please read the contents of this manual prior to operation of the unit. In addition, refer to the manuals listed below: Parts List Operation Manual of Personal Computer Software...
SAFETY PRECAUTIONS Always observe the following points before operating or inspecting a unit. DANGER Always turn off the main power supply in the facility (※1) before disconnecting the power plug. Always turn off the main power supply in the facility (※1) before inspecting the interior of the control box.
WARNING Do not touch the condenser fan while power to the unit is ON. Before removing the condenser fan cover, turn off the circuit breaker and disconnect the power plug. During air-cooled operation : Condenser fan may start and stop automatically for the refrigerant high pressure control.
CAUTION Before starting the unit, run the generator. Securely close the control box cover. Otherwise, it will allow water entry. Control box cover Quick-lock lever...
Page 7
CAUTION Wash the refrigeration unit with fresh water at PTI. Carefully flush the air-cooled condenser with fresh water to remove the salt that sticks to it.
Page 8
If any other refrigerant not specified is charged, it may cause problems with the unit. Use only Daikin specified oil (IDEMITSU, Daphne Hermetic Oil FVC46D) when replacing the refrigerant oil. If any other refrigerating machine oil not specified is charged, it may cause problems with the unit.
Page 9
CLASS 1 SPECIFIED PRODUCT BY THE HYDROFLUORIC REFRIGERANT RECOVERY LAW HFC IS USED FOR THIS PRODUCT AS A REFRIGERANT. (1) EMISSION OF HYDROFLUORIC SUBSTANCES INTO THE ATMOSPHERE WITHOUT PERMISSION IS PROHIBITED. (2) RECOVERY OF HYDROFLUORIC SUBSTANCES IS MANDATORY WHEN SCRAPPING THIS PRODUCT.
1. Introduction 1.1 OPERATION RANGE Use the units within the following range. Item Operation range Ambient temperature range -30˚C to +50˚C (-22˚F to + 122˚F) Inside temperature range -30˚C to +30˚C (-22˚F to + 86˚F) Temperature 10˚C ~ 36˚C (50˚F ~ 96.8˚F)
1.3 BASIC OPERATION OF REFRIGERATION UNIT Operate the unit by the following procedure. 1.3.1 Operation preparation (1) Make sure that the compressor discharge and suction side stop valves q, w are opened. (Refer 1.2 Basic name of components.) (2) Connect the cooling water piping to joints.
1.3.2 Starting operation (1) Make sure that power to the unit is on. (2) Connect the power plug to the power supply. Insert the plug t suited to the power source voltage, and fasten the plug firmly. (3) Turn on the main power switch of the power source facility (outside the unit) (4) Turn on the circuit breaker y.
1.3.3 Checking during operation Checking items(precautions) Method of check 1. Check the compressor, fan, pipes, etc. for abnormal noise and vibration. Visual and auditory Visual 2. Check the refrigerant for shortage. During the chilled mode, the bubbles always appear in the moisture indicator.
1.3.5 Adjust the ventilation CAUTION Adjust the opening of the lower or upper ventilator according to the cargo. When the ventilation amount is 80 m /h or more, Keep the ventilation closed during use the upper ventilator to adjust the amount.
Page 15
※ Caution for lower ventirator opening CAUTION Be sure to make the zero-point adjustment of the ventilation cover (if the ventilation amount is not more than 80 m /h) at each PTI. <Zero point adjustment procedure> While the unit is running, move the ventilation port to a fully closed position manually to set the ventilation port to "closed state"...
2.2.2 Inside LXE10E-1 q Evaporator fan motor (EFM) w Evaporator e Supply air temperature sensor (SS) Data recorder supply air temperature sensor (DSS) r Evaporator outlet pipe temperature sensor (EOS) t Evaporator inlet pipe temperature sensor (EIS) y Return air temperature sensor (RS)
Page 20
· Inside Detail RS/DRS USDA1 USDA2 USDA3 PCR, Indoor Drain Pan Heater Evaporator (Personal ※Reheater for Computor Dehumidification Control Receptacle) [Sensor] :Cargo Temperature Receptacle :Return Air Temperature Sensor for Datacorder :Supply Air Temperature Sensor for Datacorder :Evaporator Inlet Temperature Sensor...
2.2.3 Control box Inside of the control box Operation panel (Outside of the control box) Controller q Controller operation panel (EC3, 4) !3 Rechargeable battery (BAT) w MANUAL DEFROST key !4 Voltage indicator e UNIT ON/OFF key !5 Personal computer receptacle...
Page 22
· Control box Inside detail CC EFL Dip Switch for Emergency Operation (SMV adapter) CONTROLLER PCC1 (DECOS 3d) PCC2 Rechargeable battery Voltage Indicator MODEM (option) PTCT TrC (400V→24V,13V) under PTCT [Control Box] CBS :Control Box Sensor PCC1:Phace Correction Contactor 1...
Page 23
· Detail of terminal Board & Short circuit Connector Terminal Board Back of Controller Short circuit connector for emergency operation SCC1-2 (Red) Rechargeable battery board SCC2 (Blue) SCC1-1 (Blue) HuS Sensor board Connector (VOD-CPU Board) TB2, Terminal board (PPR1-PPR2)
2.3 Set point of functional parts and protection devices Device name Actuation Set point Detection method Symbol High-pressure switch 2400kPa (24.47kg/cm High-pressure switch 1900kPa (19.37kg/cm Water pressure switch 98kPa (1.0kg/cm Water pressure switch 39kPa (0.4kg/cm Chilled mode +30.0°C to –5.0°C Set point temperature (+86.0°F to –41.0°F)
2.5 OPERATION MODES AND CONTROL There are two main types of operation modes: the cargo cooling control mode and the unit inspection mode. The cargo cooling control mode is explained in this section. ※For the unit inspection mode, refer to section 3.9.
2.5.1 Frozen mode Control state transition and common control Thermostat ON (Pull-down range) Compressor Running Evaporator fan Low speed (L) Continuous compressor running for 2 minutes or more and RS SP − 1 ≤ ≤ RS > SP Pump down...
Page 31
(1) Set point temperature and control sensor When the set point temperature (referred to as SP hereafter) is –5.1˚C(+22.8˚F) or lower, the compressor is operated ON and OFF, in response to return air temperature. (2) Control qWhen the control temperature reaches SP–1.0˚C (point A),...
2.5.2 Chilled mode Control state transition and common control START SS≧SP+1.5˚C SS<SP+1.5˚C Pull-down Heat-up SS≦SP+1.5˚C RS≧SP+1.0˚C SS≧SP+5.0˚C Capacity control (SS≦SP–3.0˚C SS≧SP+1.0˚C and 3-minutes elapse) and 3-minutes SS≦SP–0.5˚C or ( and 30-minutes elapse) elapse Overcool protection SS≦SP–0.5˚C and 3-minutes elapse...
Page 33
(1) Set point temperature and control sensor ™Chilled operation When the set point temperature is –5.0˚C (–41˚F) or higher, the suction modulating valve (SMV) is controlled sensing the supply air temperature in order to adjust the cooling capacity. (2) Control...
2.5.3 Defrosting mode Start defrosting Defrost lamp (red) ON Pump down Defrosting range Compressor Evaporator fan Condenser fan ON/OFF Defrosting solenoid valve ON Hot gas solenoid valve ON Is terminating condition OK? Defrosting lamp (red) OFF Evaporator fan On after delay of 60 seconds...
Page 35
Defrosting operation (1) Defrosting system A hot-gas defrost system is adopted in the units; i.e. the high temperature and high pressure refrigerant (hot gas) from the compressor is sent to the evaporator and drain pan for defrosting. Since the evaporator is heated directly by the hot gas (refrigerant), defrosting can be performed effectively.
Page 36
(4) Defrosting termination Defrosting will be terminated when any one of the following three conditions is satisfied. qThe below figure is satisfied during defrost. Status before defrost Termination INRANGE EOS≧30.0˚C OUTRANGE EOS≧30.0˚C & RS/DRS≧15˚C w90 minutes have elapsed. eAny one of protective devices is activated.
2.5.4 Dehumidification ※If reheat coil and humidity sensor (Optional) is equipped: The unit have dehumidification control by a reheat coil, which is under the evaporator coil. To execute dehumidification, controller setting is required. (Refer to Page 3-12) In dehumidification, the Reheat Solenoid Valve (RSV)/Capillary Solenoid Valve (CSV) opens to give high pressurized refrigerant to reheat coil.
2.5.5 Common control The following are controlled in different operation modes. (For the details, refer to the following pages.) Operation mode Control name Control content Frozen Chilled Defrost The compressor is operated on and off to A Compressor ON/OFF control adjust the inside temperature.
Page 39
Common control A : Compressor ON/OFF control When the control temperature reaches the [set temperature –1.0˚C] or lower, the compressor is stopped. When the control temperature rises and becomes higher than the [set point temperature], the compressor runs again.
Page 40
In order to prevent this situation, the high pressure is controlled to be 2350kPa or lower by adjusting the opening of the suction modulating valve. • By condenser fan When the ambient temperature is low during the air-cooled operation, the condenser pressure (high pressure) will decrease.
Page 41
I : Capacity control In the chilled mode operation, adjusting cooling capacity makes the supply air temperature stable at the set point temperature (SP). The capacity control is executed by adjusting the opening of suction modulating valve (SMV) between 3 to 100 %.
Page 42
※1 If the shortage of cooling water is caused in water-cooled operation, the condensing pressure will increase, thus activating the high pressure switch. In order to prevent this event, operate the condenser fan so that the condensing pressure will not increase in excess of a high-pressure (HPT) set point.
3. ELECTRONIC CONTROLLER 3.1 Function table DECOS 3d (Daikin Electronic Controller Operation System) (Note) [PC]: Functions using personal computer Function division Function DECOS3d Control function • Temperature control • Defrosting control • Humidity control Optional Initial setting • With/without optional equipment (USDA, humidity) and horse power selection •...
Page 44
Function division Function DECOS3d Self-diagnosis and • Open-phase running automatic back-up • Over current running • CPU and peripheral device (electronic controller) Manual inspection • Compressor running hour indication • Evaporator fan individual operation (high speed) • Evaporator fan individual operation (low speed) •...
–3 –2 –1 DECOS DAIKIN ELECTRONICCONTAINER OPERATION SYSTEM Operation key q SUPPLY LED (Lights when "supply air temperature" is indicated.) u IN RANGE LED (Lights when the control temperature is in range.) w RETURN LED (Lights when "return air temperature" is indicated.) i DE-HUMID.LED...
Page 46
Function of operation key UNIT ON/OFF key UP key UNIT ON/OFF To select the item to be set in To start or to stop the unit the selected mode. operation. The controller has a memory DOWN key DOWN function.
DISPLAY q Indicate the temperature data required to be converted into "˚F" C ˚ on the LED or the LCD. DISPLAY F ˚ C ˚ Press the key, then the temperature data displayed in "˚C" is F ˚ converted into "˚F" for one minute.
3.3 Operation procedure 3.3.1 Operation procedure flow chart ※3 Battery mode Power off No key operation for 30 sec. Circuit Breaker ON Unit off I/O ON I/O OFF All Lighting (for 3 sec.) for 3 sec. Preparation Refer to (for 18 sec.)
Page 49
Check on settings and operation conditions ※1. Current indication mode (indication of operation conditions) Supply air temperature (SS) Indicates the unit operation conditions. Return air temperature (RS) P 3-9 Defrost interval Alarm Setting point humidity and humidity (OPTION) ※2. Operation setting mode...
Page 50
Indication of detailed data and alarm ※5. Sensor indication mode Discharge gas temperature (DCHS) Each sensor value can be indicated. Suction gas temperature (SGS) Modulating valve opening Fresh air quantity (FA) Electronic expansion valve opening High pressure (HPT) Supply air temperature (SS)
3.3.2 Mode operation procedure 1. CURRENT (Operation state) INDICATION MODE Supply air temperature (SS), return air temperature (RS), defrosting interval, currently existing alarm, set point humidity, and humidity are indicated. Turn on the circuit breaker and the UNIT ON/OFF key after turning the...
2. OPERATION SETTING MODE Control temperature, defrosting interval, and control humidity (optional) can be set. To change to the OPERATION SETTING MODE, press the key while CURRENT (Operation the unit is in the CURRENT INDICATION MODE. state) INDICATION MODE...
3. BATTERY MODE When commercial power is not available, the following functions are available by using the built-in wake up battery. • Indication of inside supply air temperature (SS) and return air temperature (RS) • Setting for control temperature, control humidity and defrost interval...
4. MODE OPERATION MODE Press the key in current indication mode to go to MODE operation. All indication Lights on (for 3 sec.) Starting Preparation (for 18 sec.) ※ Current indication (Operation state) MODE MODE OPERATION In mode operation, the following settings/operations are available.
Page 55
Setting item LED panel LCD panel Setting method Current indication mode –– –– –– MODE OFF, 11, 12, 13, 14, 15 G-SET Select the energy unit: kVA saving set point by G-set operation using key, Note 1) and press the key to determine the setting.
Page 56
Setting item LED panel LCD panel Setting method 95% RH~30% RH SET-SHU Select desired setting key or key, Humidity set then press key to determine. MODE ON/OFF TEST Select desired setting Test key or key, then press key to MODE determine.
5. LED display LIGHT-OFF MODE The controller LED display is turned off with this mode. ※ Activation of the panel (LED) lighting off mode. To activate the panel (LED) lighting off mode, set the LED lighting off function "dISP" in "11. Basic setting mode"...
6. SENSOR INDICATION MODE Each sensor value, the modulating valve (MV) opening, the electronic expansion valve (EV) opening and the fresh air quantity (FA) can be checked. The following items are displayed: High pressure (HPT), low pressure (LPT), voltage (PT1), total current (CT1), compressor current (CT2),...
Page 59
6. SENSOR INDICATION MODE (continued) LED: The control temperature is displayed. CURRENT LCD: The compressor running current is displayed. SENSOR-2 (CT2) The display reads: " CT A". (In Ampere.) LED: The control temperature is displayed. AMBIENT TEMPERATURE LCD: The ambient temperature is displayed.
Page 60
6. SENSOR INDICATION MODE (continued) LED: The control temperature is displayed. PULP TEMPERATURE LCD: The pulp temperature is displayed. SENSOR 1 The display reads: " US C". (USDA 1) (In ˚C or ˚F.) LED: The control temperature is displayed.
7. TEMPERATURE RECORD SCROLL MODE The control sensor value record is shown in sequence (scroll) starting with the latest data. The latest control temperatures for a maximum of 7 days are displayed. <Mode selection procedure> All indication Lights on (for 3 sec.)
Page 62
Temperature record scroll function The control sensor value record for the last 7 days is displayed in sequence (scroll) beginning with the latest one and ending with oldest one, so that easy inspection of the previous operation data is enabled on board.
Page 63
Example of TEMPERATURE RECORD SCROLL INDICATION MODE ※ It is assumed that the control temperature is the supply air temperature (SS) and the logging interval is 1 hour, and the current date and time are June 27, 2002, 14:00.
8. ALARM RECORD SCROLL MODE The alarm record is shown in sequence (scroll) starting with the latest data. The latest alarms for a maximum of 7 days are displayed. <Mode selection procedure> All indication Lights on (for 3 sec.)
Page 65
Alarm record scroll function The alarms detected over the last 7 days are displayed on the controller which scrolls through them at the rate of one sec/alarm. < Operation procedure > The LED indicates alarm codes, and the LCD displays date and time.
(The initial setting for LXE10E-1 are underlined figures.) 2 : In CASE 5), the settings of "CHARTLS" and "USdA 1/2" shall be changed from default (Default of spare controller : CHARTLS=Off, UsdA=1) to set for LXE10E-1 as below underlined. 3 : In order to complete the setting change, CIRCUIT BREAKER shall be turned off...
Controller initial setting ※10. Optional function mode P 3-26 USDA sensor setting Dehumidification control on/off setting ※11. Basic function setting mode Controller type Logging interval Compressor unload Data recorder sensor on/off P 3-27 Power supply Reheat coil P 3-28...
Page 68
10. OPTIONAL FUNCTION SETTING MODE <Key operation to enter/exit> Power OFF Circuit Breaker ON Circuit Breaker OFF after setting change Unit OFF OFF when no setting changed) I/O ON I/O OFF All indication lights on (for 3 sec.) for 3 sec.
Page 69
11. BASIC FUNCTION SETTING MODE <Key operation to enter/exit> Power OFF Circuit Breaker ON Circuit Breaker OFF after setting change Unit OFF OFF when no setting changed) I/O ON I/O OFF All indication lights on (for 3 sec.) for 3 sec.
Page 70
To set the power input: Select "Sing" or "dUAL" on the LED when the LCD displays "OC-SET" . Whenever the key is pressed, the indication of "Sing" or "dUAL" is INPUT POWER changed. Press the key to determine the setting.
Page 71
12. OPTIONAL CONDITION SETTING MODE Key operation to enter/exit < > Power OFF Circuit Breaker ON Circuit Breaker OFF after setting change Unit OFF OFF when no setting changed) I/O ON I/O OFF All indication lights on (for 3 sec.) for 3 sec.
Page 72
12. OPTIONAL CONDITION SETTING MODE (continued) H002 code is displayed when the integrated time of Out-of "In-Range" reaches 2 hours. Select "1"hour, "2"hours, "3"hours, "4"hours, "5"hours or "10"hours on the LED H002 when the LCD displays "H002". Whenever the key is pressed, the indication of the selection from "1"hour to "10"hours changes.
Page 73
12. OPTIONAL CONDITION SETTING MODE (continued) "d2 – –" message displays the total time in hours, that the temperature was above set point +2°C. The code will be displayed after the selected time which can be set to: "1"hour, "2"hours, "3"hours, "4"hours, "5"hours, or "10"hours.
Page 74
<Key operation in this mode> Whenever the key is pressed, the indication changes. Turn OFF the power breaker to confirm the setting. To input the container I.D. (No.): CONTAINER I.D. Press the key when the LCD displays "SET I.d", then display "i.d.- (No.) INPUT...
3.4 Alarm display and back-up function 3.4.1 Alarm list Alarm Alarm Alarm content Action with alarm grouping code F101 HPS activated within 30 seconds after operation start or protection device Unit stops activated 5 times at start-up operation or Fuse 1 brown (Refer Page 7-8).
3.4.2 Back-up operation at sensor malfunction Sensor malfunction Mode Back-up content Supply air temperature Chilled The same control is executed by using DSS (optional). sensor In case of DSS malfunction, [RS–2.0˚C] is used for control. When DSS and RS are faulty, the unit should be stopped.
Page 77
Back-up for temperature sensors (EIS, EOS, SGS) at frozen mode (superheat control) Evaporator inlet sensor Evaporator outlet sensor Compressor suction gas sensor Back-up operation Normal Normal Normal superheat control Normal Normal Abnormal superheat control Liquid refrigerant back prevention Normal...
DECOS 3d controller can use Rechargeable battery. It is not possible to exchange the type of battery afterwards. The battery is positioned on CPU & I/O box in controller box. Rechargeable battery: DAIKIN original rechargeable battery, type: 6N-600AA-2 (Red wire is (+), Black wire is (−)) 3.5.2 Function This battery is used without main power supply for the following functions.
3.5.4 Battery replacement (Rechargeable battery) First, turn off the power supply to the refrigeration unit. Then, detach the cover of battery and replace the battery. At this time, be sure to use the specified type of battery. Voltage indicator...
3.6 Information interchange with personal computer The electronic controller DECOS 3d has a internal memory function to record the set point temperature, inside temperature, operation mode, occurrence alarm and the report of automatic PTI during transportation in addition to the normal operation control.
3.6.1 Data logging The data logging function is to store operation data which is generated during navigation. There are seven kinds of logging data. As to Tripdata, its logging interval can select from 15, 30, 60 (default) and 120 minutes.
3.6.2 SOFTWARE CONFIGURATION MAIN MENU SUB MENU Explanation of functions Remarks LOGGER DATA TRIP DATA Data recorded in the logger is read No information DOWNLOAD USDA DATA from the controller onto the personal appears on the 4-PULP SENSORS DATA computer (disk or hard disk).
Page 83
MAIN MENU SUB MENU Explanation of functions Remarks MAKE REPORT TRIP REPORT Reports are made based on record USDA REPORT data read from the logger. 4-PULP SENSOR REPORT PTI REPORT ALARM REPORT MONITOR REPORT EVENT REPORT MAKE SET CONTAINER I.D.
3.7 Inspection procedure for the electronic controller DECOS 3d enables the internal data of the controller CPU (RAM data) to be displayed on the monitor of a personal computer by connecting the two with a communication cable. This makes it possible to preform an easy inspection of the controller and diagnose any defect.
3.8 Controller replacement and initial setting 3.8.1 Controller replacement <Replacement procedure for the controller> (1) Remove speed bolts (2 pcs) on the controller body, then remove the connector. Be sure to keep voltage indicator, the battery and the battery fixing plate for reinstallation.
3.9. PTI (Pre-Trip Inspection) AND PERIODIC INSPECTION The controller (DECOS 3d) has the automatic PTI function, which consists of three process of SHORT PTI (referred to as S.PTI hereafter), FULL PTI (referred to as F.PTI hereafter) and MANUAL CHECK (referred to as M.CHECK hereafter)
3.9.1 Inspection item The periodic inspection and adjustment of components (if required) is recommended to ensure continued successful operation. The following table shows an example of the inspection plan. Inspection item Inspection content year 4 year 8 year Inspection for physical damage...
Page 89
Inspection item Inspection content year 4 year 8 year Dryer replacement Function inspection and replacement of liquid moisture indicator Conditions of fasteners on the refrigerant pipes and gauge pipes Condition of thermal insulation of refrigerant pipe Evaporator coil cleaning...
Page 90
Inspection item Inspection content year year year 1) Calibration 2) Sensor error inspection and replacement 3) Chart drive inspection Temperature recorder 4) Recording operation inspection inspection 5) Loose terminal 6) Chart drive dry battery inspection, and replacement 7) Check and replacement of pen...
3.9.2 Automatic PTI (Pre-Trip Inspection) The automatic PTI function is provided so as to ensure correct inspection and to shorten inspection time. (1) Appearance inspection of unit Physical damage Casing insulation through hole area Drain hose (dust and clogging) Power cable and plug damage Condition of refrigerant piping fasteners.
3.9.2.1 PTI SELECTION MODE The test mode of FULL (F.PTI), SHORT PTI (S.PTI), and MANUAL CHECK (M.CHECK) can be selected. <Mode selection procedure> Power OFF Circuit Breaker ON Unit OFF I/O ON I/O OFF All indication Lights on (for 3 sec.) for 3 sec.
Automatic PTI enable conditions Water cooled Air cooled Ambient temperature condition operation operation –10˚C < Ambient temperature ≦ 43˚C S. PTI When the ambient temperature is above 43˚C or below –10˚C, the result may be abnormal. –10˚C ≦ Ambient temperature ≦ 43˚C F.
3.9.2.3 Full PTI (F.PTI) F.PTI consists of S.PTI and operation tests. Step display and contents (step P00 to P32 are as same as S.PTI) Step Content F.PTI flow chart Check on pull-down to 0˚C Check on controllability of chilled UNIT ON/OFF key: on mode operation.
Page 95
IMPORTANT When Full PTI is executed, the following settings are reset to default. q Setting temperature : Previous setting temperature w Defrost interval : 6 Hours e Log interval : 60 minutes r Dehumidification : off t G set...
3.9.2.4 Alarm list during PTI (Pre-Trip Inspection) The alarm during automatic PTI are concerned with PTI inspection items in addition to those during normal operation. The alarms at automatic PTI are indicated in J ※※※., being separated from those during normal operation.
3.9.2.5 Manual check (M.CHECK) Since the components are operated individually differing from S.PTI and F.PTI, the steps can be respectively selected and executed. However, any error occuring during execution of M.CHECK will not be included. Turn the UNIT ON/OFF key off to terminate the M.CHECK.
Page 98
MANUAL CHECK SELECTION MODE The LED displays the values of following items: Compressor operating time, Evaporator fan motor high-speed running current, Evaporator fan motor low-speed running current, Condenser fan motor running current, Battery life, Horse power, Elapsed time after trip start, Evaporator fan motor running time, Condenser fan motor running time, and Controller software version.
3.10. CHARTLESS FUNCTION The controller provides the temperature recorder function. This function, displays the control temperature logging data during operation on the LCD panel in a simple graphic chart so that the data can be confirmed easily. (Chart indication function) The chart, temperature and alarm record scroll indication are based on the control sensor data (SS/RS).
Page 100
Displaying temperature change trend: The temperature change trend is shown in the leftmost LCD. However, this display is shown only when all segments are in the same temperature range. Trend indication Condition Temperature rise trend The latest the oldest –...
3.10.2 P code (Pull down time indication) The control temperature and pull-down time are indicated alternately during pull-down operation. When the pull-down is completed, the P code will be deleted. P001: Lasts the pull-down for 1 hour. /P002: 2 houes passed since pull-down started.
3.10.3 Chartless code display function The chartless code represents the coded inside air temperature. Select "ON" of the chartless code setting to indicate the code on the LED. For the chartless code setting, refer to the "optional conditions setting" on the page 3-29.
3.10.3.2 H-code =The alarm is displayed when the control temperature does not decrease by 3˚C or more H001 every 4 hours during pull-down operation. Inside Temperature If "t" is smaller than 3˚C, code "H001" appears. ※ This criteria (3˚C) can be adjusted from 1, 2, 5 or 10˚C.
Page 104
H005 =The alarm is displayed when the control air temperature is out of "in-range" and defrosting was performed three times while the control air temperature does not return to in-range. SP+1 30min Figure5 Out range timer H006 =Alarm is displayed when the temperature difference between the control sensor and record sensor is 2˚C for 1 hour, or more.
3.10.3.3 d-code: The d-code shows the current operation state of the unit. Example d101: • This code "d101" will be displayed when the total time above set point +1˚C reaches 1 hour. The code "d102" will then be displayed when the total time above set point +1˚C reaches 2 hours.
¡Manual defrosting initiation ¡Header information changing (*1) According to the relationship among slave modem, Master modem and controller, items which can monitor and/or command are different. Please contact DAIKIN sales office if you have a specific item to monitor/command. 3-64...
4. Service and maintenance CAUTION 4.1 Maintenance service 1. Use the pressure indicating function 4.1.1 Collection of refrigerant of the controller to check the working qWhen release the refrigerant from the pressure as much as possible refrigerant system, be sure to use a...
Page 108
Caution on the service work qBe sure not to bend the refrigerant pipe Gauge manifold when pushing the quick joint during connection work. wIf the installation fails due to movement of Passage open- /closing cock the sleeve, try it again after returning the Low-pressure side hose sleeve to the original position.
4.1.3 Automatic Pump Down An automatic pump down system is applied to the unit to prevent the unit from extra decrease of low pressure due to pump down operation or burning of scroll compressor due to a close stop valve.
Page 110
(2) Automatic pump down operation Once the automatic pump down is started, all of the service works from refrigerant collection into the receiver, to the equalizing in suction piping system, can be executed automatically. When "Good" is displayed, service works such as replacing the dryer, etc. can be conducted without any other operation.
4.1.4 Refrigerant Recovery and Charge Schematic diagram Evaporator Reheat Coil Drier Condenser (Air) Check valve Condenser (Water) ② Compressor ① ③ ⑤ ④ service port Service work Service port Remarks Take care that the high pressure at the port r High pressure &...
Page 112
(1) Operation Pressure Check eReading the pressure gauge, collect the Check high pressure from the service port w non-condensable gas repeatedly until on the compressor discharge. Check low condensing pressure equals saturated pressure from the service port q on the pressure.
Page 113
(4) Vacuum-dehydrating, and refrigerant / (b) Cylinder weight recording charging Place a refrigerant cylinder on the If all the refrigerant has leaked out and air is weighing scale, and record the weight of intermixed in the refrigeration circuit, remove the cylinder.
Page 114
If it is not reached to the specified amount due to the pressure valance, close the cock of the ref. cylinder and go to next 3 & 4. 3.Operate Automatic Pump Down first. When the compressor stops (※) during the operation, end the Auto.
2 pcs 2 pcs 1 pcs (See Note 1) Note 1. Stick the auxiliary cable connection label onto the label sticked on the compressor body. This is only for LXE10E-1. Auxiliary cable connection Cable connection label label sticked on the body...
Page 116
(2) Removal of compressor 1. Recover the refrigerant from service port r on discharge line Recover and t at receiver/water cooled condenser outlet. refrigerant (Refer to the section 4.1.4 Refrigerant Recovery and charge) 2. Close the discharge and suction side stop valves on the compressor.
Page 117
4. Tighten the mounting bolts. 435 Kgf.cm ( 42.7 N.m) LXE10E-1 5. Check that stick the auxiliary cable Connect cables connection label for LXE10E-1 is sticked onto the label for others on compressor body. This is only for LXE10E-1. Pink Gray 6.
Page 118
(4) Removal of excess refrigerant oil after compressor replacement ™When the compressor is replaced to spare The oil plug, oil level gauge and "Removing oil label" are fitted on the spare parts compressor. parts compressor, remove the excess refrigerant oil in the following procedure.
Page 119
(5) Handling method of the stop valves (1) Place of the stop valve and its kind q Stop valve at compressor suction side w Stop valve at compressor discharge side [DISCHARGE SIDE STOP VALVE] [SUCTION SIDE STOP VALVE] V S H 22C A P V S H 26Q -10S Pipe size 7/8"...
Page 120
[Attention at valve shaft Handling] 1. Don't lose the "Ring Packing" when the "cap" is removed. 2. Loosen the Grand before closing or opening the valve shaft. 3. And fasten the Grand after opening or closing the valve shaft.
4.2.2 Fan and fan motor How to use bearing drawing tool on the market. (1) Specification Bearing drawing tool Evaporator Condenser Model Propeller fan Size 440mm 300mm Model 3-phase squirrel-cage Boss induction motor When the shaft of the bearing...
4.2.3 PT and CT board (EC9756) r PTI (R-S voltage) Two function of the measuring device and t Connector (CN2) for main circuit protector are integrated on this printed-circuit board. This board works as an interface between the main circuit (high voltage) and the controller.
(2-3) Removal of mounting plate Check the following table to see if the mounting plate should be removed. If the mounting plate must be removed, remove the four screws and dismount the mounting plate. Over current setting and removal of mounting plate...
4.2.5 Thermostatic expansion valve (TEV) Model : VTX-3410DMS Binding band Water-proof tube This is an internal equalizer type of q Coil Connector thermostatic automatic expansion valve and w Lock nut installed at the inlet to the heat exchanger (i.e.,...
4.2.6 Suction modulation valve q Upper rubber e Binding band cover The flow rate of suction gas is controlled between 3 to 100% by a stepping motor in w Lower rubber cover ass'y order to conduct capacity control operation.
2. Replacement of body 4.2.7 Drier (1) Remove the coil. Refer to the section 1. The drier automatically absorbs moisture in "Replacing the coil" for removing procedure. the refrigerant while it is circulated. It also (2) Remove the heat insulator q for the SMV after commonly works as a filter to remove dust in cut the binding band w.
4.2.8 Solenoid valve (1) Replacing the coil q Remove the lead wire connector from the inside Two kinds of solenoid valves are employed for of the control box, and cut and recover the binding the unit. band which fastens the lead wire.
4.2.9 Discharge pressure regulating valve 4.2.10 Check valve Model KVR15 Model LCV(B)5 (1) Replacing the valve (1) Replacement procedure q Remove the protection cap to conduct brazing q Remove the pipe clamp which fixes the for the valve body.
4.2.11 High-pressure switch (HPS) 4.2.12 Low pressure transducer (LPT) Model ACB-KB15 Model SPCL02 Set point OFF : 2400kPa (24.47kg/cm Colour indication: Low pressure transducer: Blue : 1900kPa (19.37kg/cm Low pressure transducer: cable: White When the refrigeration pressure of the unit The LPT is located in the refrigerant circuit.
Apply the heat shrinkage tube in the 4.2.14 Water pressure switch (WPS) following position, then shrink it with hot air Type: LCB-MB10 of a dryer. Set value: OFF 98kPa (at 1.0-kg/cm pressure) w Connector 39kPa (at 0.4 kg/cm...
4.2.16 Ventilation opening detector (FA sensor) Condenser fan FA sensor Control box Ventilation cover Connector Type: 5ZZ2157 This sensor has a main unit (i.e., wire winder block and position meter) and wire block. The 4.2.17 Air-cooled condenser and evaporator...
4.2.18 Water cooled condenser 4.2.20 Liquid / Moisture indicator This water cooled condenser is of shell-and- This indicator permits checking of the flow of coil type that flows cooling water in the cooling refrigerant and moisture content in the pipes and refrigerant in the shell and adopt the refrigerant.
4.2.21 Evacuation and dehydrating Boiling point of water (˚C) Atmospheric pressure(mmHg) Vacuum degree(mmHg) After repairing the refrigerant system, vacuum- –705 dehydrate the system before charging the –724 26.7 –735 refrigerant. 24.4 –737 Vacuum-dehydrating is the process to make the 22.2...
Page 134
Vacuum holding test qVacuum-dehydrating (first time) Hold the system at a pressure of ..2 hours wVacuum-breaking (first time) –755mmHg or lower for 1 hour or longer, and confirm that the vacuum reading does Nitrogen gas is pressurized to 0.5kg/cm not rise on the vacuum gauge.
Type of USDA sensor should be set. 5.1.3 USDA sensor calibration USDA requires sensor calibration every transportation and report each offset figure. Free-supply downloading software enable to assist this. Please refer to "Operation manual for Daikin Container Communication Software". 5.1.4 USDA transportation requirement Cargo and refrigeration unit shall be required pre-cooling before cargo loading.
Page 136
An example of installation of USDA receptacle inside USDA sensor receptacles Cargo temperature sensor receptacle PC port receptacle USDA sensor (type 2) Connect to receptacle...
6. TROUBLESHOOTING 6.1 Refrigeration system and electrical system If the unit does not work properly, refer to the following table to find causes of trouble and provide appropriate measures. State Malfunction occurrence Abnormal point Possible cause q No trouble with unit A.
Page 138
State Malfunction occurrence Abnormal point Possible cause C. Condenser fan rotates, q Activation of Short circuit of condenser fan motor but evaporator fan and high-pressure switch Wrong installation of condenser fan compressor do not (Water cooled Reverse rotation of condenser fan rotate.
Page 139
State Malfunction occurrence Abnormal point Possible cause E. Defrosting is operated q No trouble with the unit Excessive amount of moisture in cargo w Defrost timer frequently. Short setting timer q Container F. Refrigeration unit is High cargo temperature...
Page 140
State Malfunction occurrence Abnormal point Possible cause "Abnormal Ventilator Displayed ventilator The ventilator opening detector (VOD) is short- Opening" display opening value remains circuited. the same even by sliding The fixing screws of the VOD's wire or the the ventilator cover.
6.2 Alarm codes on electronic controller If any alarm occurs, search its cause and repair it referring to the following table. Be sure to check the connectors in the electronic controller as the poor contact of them may cause the controller alarm codes.
Page 142
Alarm code Content Possible cause E103 Compressor thermal protector Shortage of refrigerant amount Refrigerant leakage (CTP) activates. Injection solenoid valve is not Wiring lead breakage opened. Defective wiring Coil burned out Coil fell out Injection capillary is blocked Compressor thermal protector (CTP) malfunction...
Page 143
Alarm code Content Possible cause E201 Pump-down does not end Injection solenoid valve does Wrong wiring within 60 seconds. not close. Coil burned out Coil fell out Leakage of hot gas solenoid valve Valve blocked with contamination Defrosting solenoid valve...
Page 144
Alarm code Content Possible cause E407 Evaporator inlet sensor (EIS) Line breakage malfunction Short circuit Wrong wiring CPU board malfunction E409 Evaporator outlet sensor Line breakage (EOS) malfunction Short circuit Wrong wiring CPU board malfunction E411 Ambient sensor (AMBS)
Page 145
Malfunction and Alarm when the socket is disconnected or loosened. Malfunction or Alarm Location Socket No. when the socket is disconnected or loosened. CN81 No Alarm······No power supply to Controller (White) CN82 (Red) No Alarm······No power supply to Controller...
6.3 Troubleshooting for automatic PTI (J-code) Step Content Alarm Conclusion Possible cause Check method code Basic data record No judgment indication Alarm check on all Same as Same as normal Same as normal operation Same as normal sensor normal...
Page 147
Step Content Alarm Conclusion Possible cause Check method code Check on J221 BSV does not BSV coil malfunction Check on BSV coil, wiring discharge gas by- open. and terminals. pass solenoid BSV malfunction Check on outlet piping valve (BSV)
6.4 Emergency operation 6.4.1 Emergency operation of controller In case of the controller malfunction, emergency operation can be executed by using emergency operation kit. (1) Components to be prepared (emergency operation kit) Short circuit connector --- Stored on the back of CPU/IO board case in the control box.
6.4.2 Short circuit operation of controller q Turn the circuit breaker OFF. For cutting off Disconnect CN82 (White) the power to CPU board SMV adapter w Disconnect the power supply connector CN82(White) on SMV adapter board. Open cover e Remove Short Circuit Connector...
6.4.3 Opening adjustment of electronic expansion valve In case of the controller malfunction or faulty electronic expansion valve coil, electronic expansion valve can be operated with fixed valve opening by using emergency cap. Caution If the electronic expansion valve is energized while the coil is removed from valve body, the coil driver with which the valve needle is pushed protrude excessively.
6.4.4 Emergency operation of suction modulation valve: In case of emergency, there are two ways to open the suction modulating valve manually. It is important to follow these steps in this sequence. Use step 1 first. If this is not working, then use step 2.
6.4.5 Automatic Back up for supply / return air temperature sensors When the unit is equipped with the data recorder sensors, the following emergency operations are available. When the DRS and DSS are used for the emergency operation, DATA RECORDER SENSOR ON/OFF SETTING to be set OFF.
7. APPENDIX 7.1 Standard tightening torques for bolts Tightening torque Bolt size Main part kgf cm lbf ft Small parts Solenoid valve Access panel Evaporator fan motor Condenser fan motor 12.3 Control box Service door Evaporator fan motor mounting base Compressor suction flange 25.2...
7.4 Resistance of motor coil and solenoid valve coil Value of resistance Ω Symbol Parts name Remarks Compressor motor coil 1.780Ω(@75˚C) Condenser fan motor coil 57.2Ω Evaporator fan motor coil 19.4Ω Liquid solenoid valve coil Hot gas solenoid valve coil...
7.12 Pilot lamps Four pilot lamps which indicate operating mode are mounted on the controller in the control box. Pilot lamp Color Operating condition COMP. Green The compressor is running DEFROST The unit is under defrosting operation The inside temperature is within the proper range...