Instructions for the heat exchanger control system SILVER C
RX, RECOnomic, sizes 100/120, RECOsorptic, sizes 50-120
1. General
The heat exchanger control system is a control system for
380 W step motors. It is designed for precise and quiet
control of rotary heat exchangers in the SILVER C RX
ventilation units with standard rotor (RECOnomic) in size
100/120, and with sorption rotor (RECOsorptic) in sizes
05-120.
Integrated functions:
• 0 - 10 V DC analogue input for controlling the speed.
• Alarm for overloading, over-voltage and under-voltage.
• Protective motor switch with integrated current limit-
ing function.
• Short-circuit protected inputs and outputs.
• Digital input for start/stop.
• Digital input for alarm resetting.
• Integrated EMC filter.
In the size 50-80 SILVER C units the heat exchanger
control system is located inside the filter section in the
lower level. In the size 100/120 SILVER C units the heat
exchanger control system is located inside the fan or filter
section to the left of the centre section in the lower level
(viewed from the inspection side). For access, open the
inspection door.
Forbidden to start operation
It is absolutely forbidden to start operation until the
entire air handling unit, where the above-mentioned heat
exchanger control system is integrated, has been declared
to conform to relevant regulations in Machinery Directive
98/37/EEC and to existing national legislation, if applica-
ble.
The heat exchanger control system must not be energized
until the entire installation conforms to the provisions in
ALL relevant EU Directives. If the heat exchanger control
system has been damaged, for instance during transport,
it must be inspected and repaired by qualified personnel
before the voltage is connected.
Safety functions
The heat exchanger control system is protected against
phase-to-phase short.circuiting, and has integrated cur-
rent limiting function for protection of the motor.
We reserve the right to alter specifications.
The electrician is accountable for ensuring correct earth-
ing as well as protection according to local standards
and regulations. An earth fault circuit breaker, multiple
protective earthing or ordinary earthing can be used as
extra protection, provided that the local regulations are
complied with. The earth leakage currents exceed 3.5 mA.
Therefore a fixed, permanent installation and heavy-duty
protective earthing are required.
NOTE! If an earth fault occurs, there can be a direct cur-
rent component in the leakage current. Earth fault circuit
breakers should therefore be designed to be able to detect
this and be installed according to applicable national and
international regulations, where they are used.
GB.EXCHSILV2.141119
www.swegon.com
1

Advertisement

Table of Contents
loading

Summary of Contents for Swegon SILVER C

  • Page 1 In the size 50-80 SILVER C units the heat exchanger control system is located inside the filter section in the lower level. In the size 100/120 SILVER C units the heat exchanger control system is located inside the fan or filter section to the left of the centre section in the lower level (viewed from the inspection side).
  • Page 2: Technical Data

    Warning! Do not repair the heat exchanger con- trol system at the site. Never attempt to repair a defective control system unit. Contact the supplier to obtain a replacement unit. www.swegon.com We reserve the right to alter specifications.
  • Page 3 Terminals 11 (Alarm reset) and 12 ( ) (See Fig. 2). The alarm output can also be reset by switch- ing off the supply voltage to the heat exchanger control system for more than 60 seconds. www.swegon.com We reserve the right to alter specifications.
  • Page 4: Electrical Connections

    Connect the sensor cable of the rotation monitor to Terminals 9 (digital in), 10 ( ) and 15 (+10 V out, power supply to sensor). Fig. 5. Junction box, overview of the wiring terminals www.swegon.com We reserve the right to alter specifications.
  • Page 5 In the size 50-80 SILVER C units the heat exchanger control system is located inside the filter section in the lower level. In the size 100/120 SILVER C units the heat exchanger control system is located inside the fan or filter section to the left of the centre section in the lower level (viewed from the inspection side).
  • Page 6: Troubleshooting

    Terminals (GND) and Overloaded motor Remedy the overload condition of the motor ¤) "Alarm Reset". Defective motor Replace the motor ¤) Overloaded motor Remedy the overload condition of the motor ¤) www.swegon.com We reserve the right to alter specifications.
  • Page 7: Service And Maintenance

    GB.EXCHSILV2.141119 6. Service and maintenance No particular maintenance is required. Contact Swegon if any problem arises. To troubleshoot the unit: See Section 5. Troubleshooting. 7. Alarm The integrated alarm relay in the junction box has nor- mally-closed contacts and is marked "Alarm Relay". The alarm relay contacts are closed in deenergized condition and open in faultless condition.