Swegon MIRU Function Manual

Gold/miruvent fan control system
Hide thumbs Also See for MIRU:

Advertisement

Quick Links

MIRU Control Function Guide,
GOLD/MIRUVENT
1. General
The MIRU fan control system can control one type MIRU-
VENT power roof ventilator.
Up to ten power roof ventilators with MIRU Control
equipment can be connected to one GOLD air handling
unit by means of bus communication (requires GOLD
program version 6.03 or better).
This guide is meant for use as guidance in the electrical
wiring and commissioning of MIRU Control equipment in
combination with a MIRUVENT power roof ventilator. The
function guide also deals with the electrical connections
betweenMIRU Control and GOLD air handling units.
The fan motor in the MIRUVENT power roof ventilator
should be a type AC motor with integrated frequency
inverter, or EC motor with integrated motor control system
that communicates with MIRU Control via Modbus.
Swegon reserves the right to alter specifications.
2. Material Specification
Control of MIRUVENT fan via MIRU Control:
MIRU Control equipment
MIRUVENT fan with type code
x = model and size codes
Pressure sensor, pressure regulation
Pressure sensor, flow measurement
aa = code for cable length in metres.
The cable from the pressure sensors must be long enough
to reach the MIRU Control equipment.
Outdoor temperature sensor
Wiring to the GOLD unit:
Connection kit:
Contains cable adapter and communication cable.
Miscellaneous:
3-wire cable for communication to the MIRUVENT fan:
2-wire cable for possible outdoor temperature sensor.
Cable for supply voltage to MIRU Control, 230 V.
Cable for supply voltage to the MIRUVENT fan.
1 x 230 V or 3 x 400 V, see separate installation instruc-
tions for the MIRUVENT.
* At least one pressure sensor for either pressure regulation or flow
measurement is mandatory. Two pressure sensors are possible, one for
pressure regulation and one for reading the flow.
** For outdoor temperature compensation only
GB.FUNKMIRU.121204
TBMZ-11
MIRU-x-xx-xx-3-0
or
MIRU-x-xx-xx-1-x
TBLZ-1-23-aa*
TBLZ-1-23-aa*
TBLZ-1-25-2**
TBLZ-1-64
www.swegon.com
1

Advertisement

Table of Contents
loading

Summary of Contents for Swegon MIRU

  • Page 1 MIRU Control Function Guide, GOLD/MIRUVENT 1. General 2. Material Specification The MIRU fan control system can control one type MIRU- VENT power roof ventilator. Control of MIRUVENT fan via MIRU Control: Up to ten power roof ventilators with MIRU Control...
  • Page 2: Basic Installation Diagram

    If shield is to be used, the shield must be connected to the If shield is to be used, the shield must be con- AHUs'/roof fans' chassi and not connected to MIRU Control nected to the AHUs'/roof fans' chassi and not...
  • Page 3 Wiring the connections to MIRU Control Connect the 3-wire cable to terminals 11 (A), 12 (B) and 13 (GND) on the control circuit card inside the MIRU Con- trol unit. See illustration. A twisted-pair cable is recommended. 9 10 11 12 13 14 15 16 17 18 19 20 21 A B GND A B INT.BUS(FAN)
  • Page 4 Notches for running cables (2 channels) TBLZ-1-23-aa pressure sensor Connect modular cable(s) to MIRU Control in modular connection X10 and/or X11. See illustration. 9 10 11 12 13 14 15 16 17 18 19 L N PE...
  • Page 5 B to terminal 3 and GND to terminal 1. See illustration. Control circuit card, MIRU Control If more than one MIRU Control unit are to be wired to one GOLD unit, see Section 4.1 MIRU Control to GOLD in separate MIRU Control installation instructions. Wiring terminal, cable adapter www.swegon.com...
  • Page 6 GOLD unit, the MIRU Control that is last in the communi- cation loop should have its jumper JP2, ”TERM. ON OFF”, set to the ON position. Jumper JP2 of the other MIRU Con- 9 10 11 12 13 14 15 16 17 18 19 20 21 trol units should be set to the OFF position.
  • Page 7 GB.FUNKMIRU.121204 6. Settings, MIRU Control panel When you energize MIRU Control, a number of settings must be made on the control panel. For particulars on how to use the control panel, see the separate installation instructions for MIRU Control. Fan size...
  • Page 8: Service Menu

    In the GOLD unit’s hand-held micro terminal (under instal- lation – Functions – MIRU Control – Functions OFF/ON), set Fan 1 = Active. If several MIRU Control units are con- nected, these fans should also be set = Active. www.swegon.com...
  • Page 9: Operating Mode Settings

    Indicates that the MIRUVENT is controlled by any of the exter- For further information about the control panel, see the nal inputs: stop, low speed or high speed. separate installation instructions for the MIRU Control Indicates that the MIRUVENT is controlled by the internal time equipment.
  • Page 10: Installation

    *FUNCTIONS* TEMPERATURE lation – Functions – MIRU Control – Functions OFF/ON), FLOW/PRESSURE set Fan 1 = Active. If several MIRU Control units are con- FILTERS nected, these fans should also be set = Active. OPERATION Under Miru Control – Operation, you must select the fol- HEATING lowing for each fan (Fan no.):...
  • Page 11: Troubleshooting

    11 flashes Memory circuit failure These defects can be read in the menu on the MIRU Con- trol panel, for example No. 1 Fan tripped. To reset alarms. Switch off the supply voltage to the AC motor and fre- quency inverter control system so long that the internal condensers become de-energised (approx.
  • Page 12 GB.FUNKMIRU.121204 10.3 MIRU Control Seven different alarms can be shown on the display screen on the control panel of the MIRU Control. No. 1 FAN TRIPPED The motor control system of the MIRUVENT fan has tripped and initiated a group alarm. To reset the alarm, see Section 10.1 on how to reset alarms.

Table of Contents