There are substitute parts available that are incorrectly labeled as UL component parts, some are advertised as Amerex type. None of these meet UL requirements, and all of them void the Amerex extinguisher warranty and UL listing. DO NOT SUBSTITUTE.
Page 3
4. Check the date of manufacture on the extinguisher cylinder hanger loop or on the extinguisher nameplate. Cylinder must be hydrostatically tested every 5 years to the test pressure indicated on the label. REPLACE EXTINGUISHING AGENT WITH NEW AMEREX CHARGE AT TIME OF HYDROTEST. 5. Visually inspect the pressure gauge: a.
Page 4
5. Remove fill tube. Rinse the cylinder with clean water, and inspect the interior following CGA Visual Inspection Standard, Pamphlet C-6. Replace fill tube. 6. Model B260 (6 liter) – Recharge using the Model 530-2 Liquid Charge following the instructions on the package.
Page 5
Leak in the cylinder "Rejected" and return to owner. Broken footstand Install new footstand (PN 03109). FOR REPLACEMENT PARTS SEE THE AMEREX PORTABLE AND WHEELED PARTS BOOK PN 27277 AVAILABLE AT http://www.amerex-fire.com UNDER MANUALS OF THE RESOURCE SELECTION. PN 13259...