HDR DIN rail power supply(Series:HDR-15, HDR-30, HDR-60, HDR-100)
HDR-15-5
HDR-15-12
HDR-15-15
HDR-15-24
HDR-15-48
HDR-30-5
HDR-30-12
HDR-30-15
HDR-30-24
HDR-30-48
HDR-60-5
HDR-60-12
HDR-60-15
HDR-60-24
HDR-60-48
HDR-100-12
HDR-100-15
HDR-100-24
HDR-100-48
HDR-100-12N
HDR-100-15N
HDR-100-24N
HDR-100-48N
 Introduction
HDR is a DIN rail power supply series with ultra slim appearance and full range AC input (100-240Vac). The series
conforms to EN6100-3-2, the norm the European Union regulates for harmonic current. With plastic housing, it can
effectively prevent user from electric hazards. Like other Mean Well's DIN series, they can be mounted on a TS35
Standard DIN rail.
 Installation
(1)Always allow good ventilation clearances, 5mm left and right, 40mm above and 20mm below, around the unit
in use to prevent it from overheating. Also a 10-15 cm clearance must be kept when the adjacent device is a
heat source.
(2)The appropriate mounting orientation for the unit is vertical, the input terminals at the bottom and output on
the top. Mounting orientations other than that, such as upside down, horizontal, or table-top mounting, is not
allowed.
Installation Manual
INPUT: 100-240VAC 0.5A 50/60Hz
INPUT: 100-240VAC 0.5A 50/60Hz
INPUT: 100-240VAC 0.5A 50/60Hz
INPUT: 100-240VAC 0.5A 50/60Hz
INPUT: 100-240VAC 0.5A 50/60Hz
INPUT: 100-240VAC 0.88A 50/60Hz
INPUT: 100-240VAC 0.88A 50/60Hz
INPUT: 100-240VAC 0.88A 50/60Hz
INPUT: 100-240VAC 0.88A 50/60Hz
INPUT: 100-240VAC 0.88A 50/60Hz
INPUT: 100-240VAC 1.8A 50/60Hz
INPUT: 100-240VAC 1.8A 50/60Hz
INPUT: 100-240VAC 1.8A 50/60Hz
INPUT: 100-240VAC 1.8A 50/60Hz
INPUT: 100-240VAC 1.8A 50/60Hz
INPUT: 100-240VAC 3.0A 50/60Hz
INPUT: 100-240VAC 3.0A 50/60Hz
INPUT: 100-240VAC 3.0A 50/60Hz
INPUT: 100-240VAC 3.0A 50/60Hz
INPUT: 100-240VAC 3.0A 50/60Hz
INPUT: 100-240VAC 3.0A 50/60Hz
INPUT: 100-240VAC 3.0A 50/60Hz
INPUT: 100-240VAC 3.0A 50/60Hz
OUTPUT: 5V 2.4A
OUTPUT: 12V 1.25A
OUTPUT: 15V 1.0A
OUTPUT: 24V 0.63A
OUTPUT: 48V 0.32A
OUTPUT: 5V 3.0A
OUTPUT: 12V 2.0A
OUTPUT: 15V 2.0A
OUTPUT: 24V 1.5A
OUTPUT: 48V 0.75A
OUTPUT: 5V 6.5A
OUTPUT: 12V 4.5A
OUTPUT: 15V 4.0A
OUTPUT: 24V 2.5A
OUTPUT: 48V 1.25A
OUTPUT: 12V 7.1A
OUTPUT: 15V 6.13A
OUTPUT: 24V 3.83A
OUTPUT: 48V 1.92A
OUTPUT: 12V 7.5A
OUTPUT: 15V 6.5A
OUTPUT: 24V 4.2A
OUTPUT: 48V 2.1A

Advertisement

loading
Need help?

Need help?

Do you have a question about the HDR-15 Series and is the answer not in the manual?

Questions and answers

Summary of Contents for MW HDR-15 Series

  • Page 1 Installation Manual  Type: HDR DIN rail power supply(Series:HDR-15, HDR-30, HDR-60, HDR-100) HDR-15-5 INPUT: 100-240VAC 0.5A 50/60Hz OUTPUT: 5V 2.4A HDR-15-12 INPUT: 100-240VAC 0.5A 50/60Hz OUTPUT: 12V 1.25A HDR-15-15 INPUT: 100-240VAC 0.5A 50/60Hz OUTPUT: 15V 1.0A HDR-15-24 INPUT: 100-240VAC 0.5A 50/60Hz OUTPUT: 24V 0.63A HDR-15-48 INPUT: 100-240VAC 0.5A 50/60Hz...
  • Page 2 Installation Manual (3)Use copper wire only, and recommended wires are shown as below. Rated Current of Equipment (Amp) Cross-section of Lead(mm Note:Current each wire carries should be de-rated to 80% of the current suggested above when using 4-6 wires connected to the unit. Make sure that all strands of each stranded wire enter the terminal connection and the screw terminals are securely fixed to prevent poor contact.
  • Page 3 Installation Manual  Warning / Caution !! “CAUTION:FOR USE IN A CONTROLLED ENVIRONMENT. REFER TO MANUAL FOR ENVIRONMENTAL CONDITION” ATTENTION: A UTILISER DANS UN ENVIRONNEMENT CONTROLE. REFEREZ VOUS AU MANUEL POUR LES CONDITIONS D’ENVIRONNEMENT. (1)Risk of electrical shock and energy hazard. All failure should be examined by a qualified technician. Please do not remove the case of the power supply by yourself! (2)Risk of electric arcs and electric shock (danger to life).

This manual is also suitable for:

Hdr-30 seriesHdr-60 seriesHdr-100 seriesHdr-15-5Hdr-15-12Hdr-15-15 ... Show all