8. Technical data
8. Technical data of the automatic transfer switch
ATS021
ATS021
Operating voltage
Main voltage
Phase voltage
Rated frequency
Rated impulse withstand voltage U
Voltage and frequency sensing precision
Voltage
Frequency
Relay utilization category
1/3 phase
Over voltage category
IP rating
Temperature area
Transportation and storage temperature
Altitude
Humidity r.h. = 95 % T = 25...55 °C
with condensation
without condensation
Table 8.1
Technical data of ATS021
imp
Installation and operating instructions, ATS021
Value
208Vac - 480 Vac ±20 %
120Vac - 277 Vac ±20 %
50 Hz, 60 Hz ±10 %
6 kV
5 %
1 %
8 A, AC1, 250 V
III, U
6 kV
imp
IP20 for the front panel
-20... +60 °C
-40... +90 °C
Max. 2000 m
5 % - 98 %
5 % - 90 %
1SDH000759R0002, L4106