SURAN ENDA EHTC7425A Manual

Humidity and temperature controller

Advertisement

Quick Links

Read this document carefully before using this device. The guarantee will be expired by
damaging of the device if you don't attend to the directions in the user manual. Also we don't
accept any compensations for personal injury, material damage or capital disadvantages.

ENDA EHTC7425A HUMIDITY AND TEMPERATURE CONTROLLER

Thank you for choosing
7 x
2
72
mm sized
Dual 4 digits display
0/4-20mA, 0-10V, 1- 5V analog or digital input (Specify at Order)
Heating or cooling control selection
PID, On-Off Temperature control selection
PID Auto-calculation (SELF TUNE)
Humidification or drying control selection
Internal supply output for sensor
Timer control for fan relay output
2 Relay outputs with time setting for incubation operations
Adjustable buzzer alarm feature for measurement values
CE marked according to European Norms.
Order Code : EHTC7425A -
1 -
Input
2 -
AS.......Analog Input
DS......Digital Input
Sensor must be ordered separately.
TECHNICAL SPECIFICATIONS
ENVIRONMENTAL CONDITIONS
Ambient/stroge temperature
Max. Relative humidity
Rated pollution degree
Height
Do not use the device in locations subject to corrosive and flammable gases.
ELECTRICAL CHARACTERISTICS
Supply
Power consumption
Wiring
Temperature input range
Humidity input range
EMC
Safety requirements
INPUTS
Input Type
Measurement Range
0-20mA
4-20mA
AS
1-5V
-40.0....125.0 C
0-10V
0....100 %RH
DS
EHTD-CB-100
When the device is in current measurement mode, the input impedance is 10 . Therefore voltage input should not be connected to the device while
in current mode. Otherwise the device will deteriorate. If it is necessary to switch from the voltage measurement mode to the current measurement
mode while the device is running, It must be removed and then changed to one of the input type current measurement modes.
OUTPUT
Sensor Supply
15VDC , Max. 50mA
Life expectancy for relay
30.000.000 Switching for no-load operation; 300.000 switching for 10A resistive load at 250VAC.
HOUSING
Housing type
Suitable for flush-panel mounting according to DIN 43 700.
W72xH72xD97mm
Weight
Approx. 350g (after packing)
Enclosure Material
Self extinguishing plastics
While cleaning the device, solvents (thinner, gasoline, acid etc.) or corrosive materials must not be used.
SURAN
Industrieelektronik
Dettinger Str. 9
/ D-72160 Horb a.N
ENDA EHTC7425A
Humidity and Temperature Controller
-
-
1
2
3
Supply Voltage
4 ModBus
-
230..........230V AC
Blank......N/A
SM..........9...30V DC
RS ...... ModBus
I
7...24V AC
0 ... +50°C/-25 ... 70°C (Without icing)
80
%
Relative humidity for temperatures
According to EN 60529
Front panel : IP6
Max. 2000m
230V AC ±10%, 50/60Hz or 9...30V DC / 7...24V AC
Max. 7VA
2.5mm² screw-terminal connections
0~20mA / 0~10V can be selected for analog output sensors. Temperature range for digital output Enda Sensor is -40~125°C
0~20mA / 0~10V can be selected for analog output sensors. Humidity range for digital output Enda Sensor is 0~100 RH
EN 61326-1: 2013
EN 61010-1: 2010 (pollution degree 2, overvoltage category II)
Measurement Accuracy
±%0,5 (Full scale)
º
Tel.: +49 (0)7451 / 625 617
Fax: +49 (0)7451 / 625 0650
...
(
Specify at Order .
)
up to 31
°C decreasing linearly
,
5
,
Rear
panel : IP20
Input Resistance
Approx. 10Ω
Approx. 100kΩ
---------------
Ω
E-mail : info@suran-elektronik.de
Internet : www.suran-elektronik.de
EHTC7425A
HEAT
%RH
Fan
L
Rotate
R
SET
TSET
C(on/off)
HSET
HUMIDITY TEMPERATURE CONTROLLER
to
50% at 40°C.
EHTC7425A-E-10052019
english
°C
%RH
1 / 7
.

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ENDA EHTC7425A and is the answer not in the manual?

Questions and answers

Summary of Contents for SURAN ENDA EHTC7425A

  • Page 1 Also we don't accept any compensations for personal injury, material damage or capital disadvantages. ENDA EHTC7425A HUMIDITY AND TEMPERATURE CONTROLLER ENDA EHTC7425A Thank you for choosing...
  • Page 2 These cables should not be close to the power cables or components. The installation and electrical connections must be carried on by a qualified staff and must be according to the relevant locally applicable regulations. SURAN Industrieelektronik Tel.: +49 (0)7451 / 625 617 E-mail : info@suran-elektronik.de EHTC7425A-E-10052019 Dettinger Str. 9 / D-72160 Horb a.N Fax: +49 (0)7451 / 625 0650...
  • Page 3 ROTATION RELAY ROTATION RELAY 3. / 7 SURAN Industrieelektronik Tel.: +49 (0)7451 / 625 617 E-mail : info@suran-elektronik.de EHTC7425A-E-10052019 Dettinger Str. 9 / D-72160 Horb a.N Fax: +49 (0)7451 / 625 0650 Internet : www.suran-elektronik.de...
  • Page 4 PID parameters. not be changed. 5ucc 1000 1000 4. / 7 SURAN Industrieelektronik Tel.: +49 (0)7451 / 625 617 E-mail : info@suran-elektronik.de EHTC7425A-E-10052019 Dettinger Str. 9 / D-72160 Horb a.N Fax: +49 (0)7451 / 625 0650 Internet : www.suran-elektronik.de...
  • Page 5 The marked parameters are valid only for the humidity temperature sensor model with analogue input. 5. / 7 SURAN Industrieelektronik Tel.: +49 (0)7451 / 625 617 E-mail : info@suran-elektronik.de EHTC7425A-E-10052019 Dettinger Str. 9 / D-72160 Horb a.N Fax: +49 (0)7451 / 625 0650...
  • Page 6 A. h Lo A. h H5 Humidity alarm hysteresis. 6. / 7 SURAN Industrieelektronik Tel.: +49 (0)7451 / 625 617 E-mail : info@suran-elektronik.de EHTC7425A-E-10052019 Fax: +49 (0)7451 / 625 0650 Dettinger Str. 9 / D-72160 Horb a.N Internet : www.suran-elektronik.de...
  • Page 7 Communication speed (baud rate) selection 19. 2 0 9600 baud 7. / 7 SURAN Industrieelektronik Tel.: +49 (0)7451 / 625 617 E-mail : info@suran-elektronik.de EHTC7425A-E-10052019 Fax: +49 (0)7451 / 625 0650 Dettinger Str. 9 / D-72160 Horb a.N Internet : www.suran-elektronik.de...
  • Page 8 ENDA EHTC7425A HUMIDITY AND TEMPERATURE CONTROLLER MODBUS ADDRESS MAP HOLDING REGISTERS Holding Register Read / Write Data Parameter Permission Addresses Data Content Type Name Decimal t. 5 Et 0000d Temperature set value 0x0000 word R / W t. u PL...

Table of Contents