Zander Aachen SR3C Operating Instructions

Zander Aachen SR3C Operating Instructions

Emergency stop safety relay

Advertisement

Quick Links

Emergency Stop Safety Relay SR3C
Operating Instructions
The SR3C is a universal emergency stop safety switching device
Correct Use
with three safe relay contactss that can quickly and safely stop
the moving parts of a machine or system in case of danger.
Applications for the SR3C include single or dual-channel emer-
gency stop circuits and guard monitoring on machines and
plants.
3 safe, redundant relay contacts
1 auxiliary contact (signaling contact)
Connection of:
- Emergency stop buttons
- Safety switches
- Non-contact safety switches
- OSSD-Outputs
Single and dual-channel operation possible
Feedback loop for monitoring downstream contactors or
expansion modules
Cyclical monitoring of the output contacts
Indication of the switching state via LED
Function
The emergency stop safety switching device SR3C is
designed for safe isolation of safety circuits according to
EN 60204-1 and can be used up to safety category 4, PL e
according to EN ISO 13849-1.
The internal logical system closes the safety contacts when
the start button is pressed.
If the safety switch is opened, the positively driven safety
contacts are opened and safely switch the machine off. It is
ensured that a single fault does not lead to a loss of the
safety function and that every fault is detected by cyclical
self-monitoring no later than when the system is switched
off and switched on again.
Installation
As per EN 60204-1, the device is intended for installation in
control cabinets with a minimum degree of protection of
IP54. It is mounted on a 35 mm DIN rail according to
DIN EN 60715 TH35.
Installation and commissioning of the device must be
Safety
performed only by authorized personnel.
Precautions
Observe the country-specific regulations when installing
the device.
The electrical connection of the device is only allowed to
be made with the device isolated.
The wiring of the device must comply with the instruc-
tions in this user information, otherwise there is a risk
that the safety function will be lost.
It is not allowed to open the device, tamper with the
device or bypass the safety devices.
Electrical
Consider the information in the section "Techn. data"
Connection
When the 24 V version is used, a safety transformer
according to EN 61558-2-6 or a power supply unit with
electrical isolation from the mains must be connected.
External fusing of the safety contacts must be provided
If the device does not function after commissioning, it
must be returned to the manufacturer unopened. Ope-
ning the device will void the warranty
Use adequate protective circuit for inductive loads (e.g.
free-wheeling diode)
H. ZANDER GmbH & Co. KG • Am Gut Wolf 15 • 52070 Aachen • Germany
Tel +49 (0)241 9105010 • Fax +49 (0)241 91050138 • info@zander-aachen.de • www.zander-aachen.de
Errors and technical changes reserved
Germanischer Lloyd
Certifikat TAE00003JF
2 start behaviors possible:
- Monitored manual start
- Automatic start
Short circuit and earth fault monitoring
Up to PL e, SILCL 3, category 4
Fig. 1 Block diagram SR3C
Fig. 2 Installation / removal
All relevant safety regulations and standards are to be
observed.
The overall concept of the control system in which the
device is incorporated must be validated by the user.
Failure to observe the safety regulations can result in
death, serious injury and serious damage.
Note down the version of the product (see label "Ver: x")
and check it prior to every commissioning of a new de-
vice. If the version has changed, the overall concept of
the control system in which the device is incorporated
must be validated again by the user.
A1:
A2 :
S11:
S10:
S21:
S13:
S14:
S12:
13-14:
23-24:
33-34:
41-42:
Fig. 3 Connections
English translation
Power supply
Power supply
DC 24 V control voltage
Control line
Start control line
Control line
Control line
Control line
Safety contact 1
Safety contact 2
Safety contact 3
Auxiliary contact
M03
Ver. B
E61-137-00
1

Advertisement

loading

Summary of Contents for Zander Aachen SR3C

  • Page 1 English translation Operating Instructions Errors and technical changes reserved The SR3C is a universal emergency stop safety switching device Correct Use with three safe relay contactss that can quickly and safely stop the moving parts of a machine or system in case of danger.
  • Page 2 Emergency Stop Safety Relay SR3C English translation Operating Instructions Errors and technical changes reserved Applications Depending on the application or the result of the risk assessment according to EN ISO 13849-1, the device must be wired as shown in Fig. 1 to Fig. 11.
  • Page 3 DIN rail according to EN 60715 TH35 *) If several SR3C devices are closely spaced under load, the max. total current at the ambient temperature of T=20 °C: 9 A; at T=30 °C: 3 A; at T=40 °C =1 A.
  • Page 4 Plug-In Fixed Drawing Terminals Terminals Variants Order no. 472170 SR3C, AC 230 V (50-60 Hz), fixed screw terminals Order no. 472171 SR3C, AC 115 V (50-60 Hz), fixed screw terminals Order no. 472173 SR3C, AC/DC 24 V, fixed screw terminals Order no.