With functions 5 and 6 a measuring range above and below the switch point SPx is
defined in connection with the parameter HYx (hysteresis).
• Values:
• Default value: FO1 =
SOx
Store Output (latching function output 1/2)
OFF
Inactive
Front
Active with front reset ( -button, > 3 s)
F u E
Active with front and external reset
When the latching function is active the respective output does not switch back
automatically but must be reset.
• Values: OFF, Front, FuE
• Default value: OFF (latching function inactive)
FSx
Function Signal Evaluation (signal and wire monitoring)
OFF
Inactive
on
Active
Switching characteristics of the relay outputs with inactive and active parameter FSx
Example switching functions 1 and 2:
• Values: OFF, on
• Default value: OFF (signal and wire monitoring inactive)
DMx, DIM
Dimension (unit)
• Values: °C, bar, lit, mA, no technical unit
• Default value: mA
AO3
Analogue Out3 (analogue output)
4 -20
Current range of the analogue signal
0 -20
• Values: 4-20, 0-20 [mA]
• Default value: 0...20 mA
SP =
HY =
(1),
(2),
(3),
(2), FO2 =
SP
+ SP
max
min
2
SP – SP
min
x 100 [%]
SP
(4),
(5),
(3)
AL-3
MONITOR
(6)
33