LG Multi Type Installation Manual page 13

Ceiling duct type
Hide thumbs Also See for Multi Type:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
6) Pipe bending
Annealed copper pipe with small diameter (ø6.35 or ø9.52) can be easily bent manually. In
this case, secure large R(radius) for the bend section and gradually bend pipe. If annealed
copper pipe is large in diameter (ø15.88 or ø19.05), bend pipe with bender. Use bender
appropriate for the pipe diameter.
7) Brazing
In refrigerant piping, bending (in particular, acute bending) must be minimized to reduce
piping resistance. Bending is, however, necessary in some places by virtue of the installation
position of devices auxiliary to the packaged air conditioner, or of the building structure,
piping distance or finishing appearance. If a more acute bend is required than that attainable
by pipe bender, perform brazing using ready-made elbow. Aside from this function, brazing
also serves to connect straight pipes, generally using ready-made sockets. While brazing,
protect piping against heat with wet cloth to avoid damaging valve packing or burning
thermal insulator with burner heat. While brazing, blow inert gas (nitrogen gas or carbonic
gas) to prevent formation of oxidation film in copper piping; otherwise, the refrigerant circuit
will clog. The blowing of nitrogen gas (or carbonic gas) through 3-way valves is described in
the following:
8) Refrigerant piping(Flare piping)
When connecting piping, be sure to keep piping dry(keep piping away from water), clean
(keep piping away from dust) and airtight (avoid refrigerant leakage).
When connecting piping on rainy days or making a through-hole in wall, take due care to
prevent water or plaster from entering piping.
CAUTION: This procedure is
designed to prevent formation of
oxidation film by filling piping with
inert gas. Note that excessive gas
pressure will generate pinholes at
brazed points.
(Nitrogen gas: Supply pressure
0.05~0.1kg/cm
When supplying inert gas, be sure
to open one end of piping.
2
G)
Connecting Pipes to the Indoor Unit
Water enters
Installation Manual 13
Plaster enters

Advertisement

Table of Contents
loading

This manual is also suitable for:

9k12k18k24k

Table of Contents