LG Multi Type Installation Manual page 11

Ceiling duct type
Hide thumbs Also See for Multi Type:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
INSTALLATION OF REMOTE CONTROLLER
POINT OF REMOTE CONTROLLER INSTALLATION
• Although the room temperature sensor is in the indoor unit, the remote control box should
be installed in such places away from direct sunlight and high humidity.
INSTALLATION OF THE REMOTE CONTROLLER
• Select places that is not splashed by
water.
• Select control position after receiving
customer approval.
• The room temperature sensor of the
thermostat for temperature control is built
in the indoor unit.
• This remote controller equipped with
liquid crystal display. If this position is
higher or lower, display is difficult to see.
(The standard height is 1.2~1.5m high)
ELECTRICAL WIRING TO THE INDOOR UNIT
If the length of the cord exceeds 50m, use a wire size greater than 0.5mm
DISASSEMBLING THE REMOTE CONTROLLER
Lever carefully
the box open
using a screw
driver, etc.
WHEN THE REMOTE CONTROLLER IS
INSTALLED WITH THE CORD BURIED.
PROCEDURE OF INSTALLATION
1. Fix the under plate on the switch box by
screws(Local supply). In this case, fit the under
plate on the wall, and be careful of deformation.
2. Receive the remote control cord in the switch box.
3. Hook the remote control unit on the under plate.
Face of wall
Upper notch
Under plate
Remote
control unit
Screw
(Local supply)
Remote
control cord
Lower notch
Switch box
(Local supply)
Remote controller
CN REMO
The maximum length of the cord is 100m.
Front case
Remote
control
box body
Install the remote control box
and cord correctly.
ROUTING OF THE REMOTE CONTROL CORD
• Keep the remote control cord away from
the refrigerant piping and the drain
piping.
• To protect the remote control cord from
electrical noise, place the cord at least
5cm away from other power cables.
(Audio equipment, Television set, etc)
• If the remote control cord is secured to a
wall, provide a trap at the top of the cord
to prevent water droplets from running.
(Main board)
CN REMO
Make sure that wire and terminal
numbers are matched on unit side
and remote controller side.
2
.
WHEN THE REMOTE CONTROLLER IS
INSTALLED WITH THE CORD EXPOSED.
PROCEDURE OF INSTALLATION
1. Fix the under plate on the wall by self tapping
screws (accessory).
2. Make a slit (Part A) at the top side of the remote
controller by nipper.
3.Rout the cord as shown in the following figure. In
this case, push the cord into the around of
case(Part B).
4. Hook the remote control unit on the under plate.
Remote
control cord
(Part A)
Remote
control unit
FIXING OF REMOTE
CONTROL CORD
1. Fix the cord clamps on the wall
by ø3 tapping screws(Local supply).
2. Fix the remote control cord.
Installation of Indoor
Face of wall
Upper notch
Under plate
Tapping screw
(Local supply)
Upper flange
Push hand
(Part B)
Lower notch
Cord
clamp
Installation Manual 11

Advertisement

Table of Contents
loading

This manual is also suitable for:

9k12k18k24k

Table of Contents