Download Print this page

Macurco CME1-FTG User Instructions page 3

Aerosol co field test gas

Advertisement

Testing the Fan Relay
Note: The time to activate the Fan relay depends on the delay setting.
1. With the display function turned "On", the CM-6 will show the current concentration of CO or "0" (zero) in
clean air.
2. With the cover in place, direct the gas into the housing by placing the nozzle of the aerosol can onto the
sensor grate area (under DO NOT PAINT) and press for 2 to 3 seconds.
3. When the CO concentration reaches the Fan Relay setting (35 ppm, for example) the display will flash back
and forth between "FAn" and "35". With the display function turned "Off", the display does not show the CO
concentration, but will show "FAn" as long as the fan relay is activated.
Note: If the Fan relay does not close within a few seconds, there are six possibilities:
a. The gas is empty, expired or degraded, replace the gas cylinder.
b. The gas was not directed into the housing (direct the gas into the housing by placing the nozzle of
the aerosol can onto the sensor grate area and re-test).
c. The gas concentration at the sensor did not reach the Fan relay activation level. Set Fan relay to
25ppm and repeat the test.
d. Detector has Fan relay set to disable (OFF) or 100ppm. Set Fan relay to 25ppm and repeat the
test.
e. The Fan relay delay (Frd) setting is at 3 minutes. Set the Fan relay delay to zero (0) minutes.
f. Unit needs to be re-calibrated (go through the Field Calibration Procedure and re-test).
4. Wait for the display to return to 0 ppm and configure options to desired settings.
Testing the Alarm Relay
Note: The CO concentration to activate the Alarm relay depends on the setting.
1. With the display function turned "On", the CM-6 will show the current concentration of CO or "0" (zero) in
clean air.
2. With the cover in place, direct the gas into the housing by placing the nozzle of the aerosol can onto the
sensor grate area (under DO NOT PAINT) and press for 4 to 5 seconds.
3. When the CO concentration reaches the Fan relay setting, the Fan relay should activate according to the
settings.
4. When the CO concentration reaches the Alarm Relay setting, (200 ppm, for example) the display will flash
back and forth between "ALr" and "200". The buzzer will sound indicating "Alarm" if the buzzer is turned
"On". With the display function turned off the display does not show the CO concentration, but will show
"ALr" when the Alarm relay is activated.
Note: If the Fan relay does not close within a few seconds, there are five possibilities:
a. The gas is empty, expired or degraded, replace the gas cylinder.
b. The gas was not directed into the housing (direct the gas into the housing by placing the nozzle of
the aerosol can onto the sensor grate area and re-test).
c. The gas concentration at the sensor did not reach the Alarm relay activation level. Set Alarm relay
to 50 and repeat the test.
d. Detector has Alarm relay set to disable (OFF) or 200ppm. Set Alarm relay to 50ppm and repeat the
test.
e. Unit needs to be re-calibrated (go through the Field Calibration Procedure and re-test).
5. Wait for the display to return to 0 ppm and configure options to desired settings.
3

Advertisement

loading