General Installation Information cont.
BLOWER COMPARTMENT
COIL COMPARTMENT
(Access panel removed)
)
VERTICAL DRAIN PAN
REFRIGERANT LINE
CONNECTIONS
SECONDARY DRAIN
UPFLOW 3/4" THREADED
ADE
ED
PRIMARY DRAIN UPFLOW
OW
3/4" THREADED
DUCT WORK MAY BE
Y BE
FASTENED CAUTIOUSLY
WITH SCREWS TO THE
SIDES AND REAR OF UNIT
Return Duct Attachment & Component Location
Condensate Deflector Shield
A condensate deflector shield comes attached to the
vertical A-coil drain pan. If the unit is being installed in
either the top flow or bottom flow configuration, no change
is necessary.
S-CLIPS ON HORIZONTAL PAN
Condensate Deflector on Horizontal Drain Pan Edge
FRONT VIEW
W
CONDENSATE
CONDENSATE
DEFLECTOR
SENSOR BRACKET
FEEDER
TUBES
CO
CONDENSATE
SENSOR BRACKET
CONDENSATE
DEFLECTOR
SAH AIR HANDLER INSTALLATION MANUAL
HORIZONTAL DRAIN PAN
HORIZONTAL
H
S
SECONDARY DRAIN
HORIZONTAL
PRIMARY DRAIN
AL
ALTERNATE DRAIN
CONNECTIONS
CO
UP
UPFLOW
FILTER DOOR
FI
DUCT SHOULD BE
D
TAPED TO CABINET
TA
T
FRONT BRACKET
(NO SCREWS)
WHEN ATTACHING DUCT WORK WITH SCREWS -
KEEP SCREWS WITHIN 5/8" OF SIDES AND BACK OF
AIR HANDLER. MAXIMUM LENGTH OF SCREW 3/4".
If the air handler is being installed in either horizontal
position, the condensate deflector shield will need to be
removed from the vertical pan and placed on the horizontal
pan. Remove the condensate deflector shield and the
S-clips that attach it to the vertical pan. Reposition the
condensate deflector shield and S-clips on the horizontal
drain pan.
On units that have control option 'C' the condensate sensor
bracket will also need to be moved and attached to the
horizontal pan.
Note: Condensate deflector shield should be installed in the
S-clip section which is inside the drain pan edge.
S-CLIP
FIGURE 6: S-Clip Installation
7
SIDE VIEW
RETURN AIR
DUCT
CONDENSATE
DEFLECTOR
DRAIN
PAN
WALL