General Installation Information cont.
Refrigeration
The SAH Series air handlers are supplied with an expansion
device. The txv supplied has an internal check valve so no
external check valve is necessary. Check sub-cooling and
superheat, refrigerant charge and txv may require further
adjustment.
TXV Superheat Adjustment Procedure (see figure 4)
Txv's may require adjustment for a specific application.
1. Remove the seal cap from the bottom of the valve.
2. Turn the adjustment screw counterclockwise to increase
superheat and clockwise to decrease superheat.
One complete 360° turn changes the superheat
approximately 1-2°F. You may need to allow as much as
30 minutes after the adjustment is made for the system
to stabilize.
3. Once the proper superheat setting has been achieved
replace and tighten the seal cap.
Line Set Sizes
Unit
Air
Size
Handler
Suction
022
SAH022
5/8" OD
030
SAH030
5/8" OD
036
SAH036
5/8" OD
042
SAH042
3/4" OD
048
SAH048
3/4" OD
060
SAH060
7/8" OD
070
SAH066
7/8" OD
026
SAH026
5/8" OD
038
SAH036
5/8" OD
049
SAH048
3/4" OD
064
SAH060
7/8" OD
072
SAH066
7/8" OD
CAPACITY MULTIPLIER
Notes: * The "Charge Amount with SAH Air Handler" column is based on the charge amount for a SAH Air Handler +
Compressor Section/Split.
Additional charge will need to be added accordingly for line set length.
After charge is added, additional adjustments can be made to get appropriate subcooling and superheat measurements.
Additional charge for R410A is 0.50 oz. per ft. for 3/8" and 1.0 oz. per ft. for 1/2" tube.
Longer line sets will significantly reduce capacity and efficiency of the system as well as adversely effect the system reliability
due to poor oil return.
20 feet
40 feet
Liquid
Suction
3/8" OD
5/8" OD
3/8" OD
3/4" OD
3/8" OD
3/4" OD
3/8" OD
3/4" OD
3/8" OD
7/8" OD
1/2" OD
7/8" OD
1/2" OD
7/8" OD
3/8" OD
3/4" OD
3/8" OD
3/4" OD
3/8" OD
7/8" OD
1/2" OD
7/8" OD
1/2" OD
7/8" OD
1.00
0.985
SAH AIR HANDLER INSTALLATION MANUAL
Warning – There are 12 total (360°) turns on the superheat
adjustment stem from wide open to fully closed.
When adjusting the superheat stem counterclockwise
(superheat increase) and the stop is reached, any further
counterclockwise turning adjustment will damage the valve.
Charging the System
Refer to the compressor section Installation Manual for
charging the system, checking subcooling/superheat and
unit operating parameters. Refer to the Refrigerant Line
Sizing table for initial refrigeration charge amounts used
with the split.
60 feet
Liquid
Suction
3/8" OD
3/4" OD
3/8" OD
3/8" OD
3/4" OD
3/8" OD
3/8" OD
3/4" OD
3/8" OD
7/8" OD
3/8" OD
7/8" OD
1/2" OD
1-1/8" OD
1/2" OD
1-1/8" OD
3/8" OD
3/4" OD
3/8" OD
3/4" OD
3/8" OD
7/8" OD
1/2" OD
1-1/8" OD
1/2" OD
1-1/8" OD
0.97
11
Split
Factory
Amount with
Charge
Liquid
(oz.)
Handler (oz.)
56
56
1/2" OD
56
1/2" OD
74
1/2" OD
90
1/2" OD
92
1/2" OD
108
1/2" OD
52
1/2" OD
56
1/2" OD
90
1/2" OD
96
1/2" OD
104
*Charge
SAH Air
76
82
96
104
112
119
135
72
96
112
119
133
1/13/2017

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents