Wiring Connection; Others; Gas Leak Test; Remote Control A-B Selection - Toshiba RAS SKV Series Installation Manual

Split type air conditioner
Table of Contents

Advertisement

Available languages

Available languages

Wiring Connection

1. Remove the valve cover from the outdoor unit.
2. Connect the connecting cable to the terminals as identified with their
respective matched numbers on the terminal block of indoor and outdoor
unit.
3. When connecting the connecting cable to the outdoor unit terminals, make
a loop as shown in the installation diagram of indoor and outdoor unit to
prevent water coming in the outdoor unit.
4. Insulate the unused cords (conductors) from any water coming in the
outdoor unit. Proceed them so that they do not touch any electrical or
metal parts.
Stripping length of the connecting cable
RAS-077, 107, 137SAV Series
Terminal block
Connecting cable
Power cord
RAS-167SAV Series
Terminal block
Connecting cable
Power cord

Gas Leak Test

Check places for
the indoor unit.
Check places for
the outdoor unit.

Remote Control A-B Selection

• When two indoor units are installed in the same room or adjacent two
rooms, if operating a unit, two units may receive the remote control signal
simultaneously and operate. In this case, the operation can be preserved
by setting either one remote control to B setting. (Both are set to A setting
in factory shipment.)
• The remote control signal is not received when the settings of indoor unit
and remote control are different.
• There is no relation between A setting/B setting and A room/B room when
connecting the piping and cables.
To separate using of remote control for each indoor unit in case of 2 air
conditioner are installed near.
Remote Control B Setup.
1. Press [RESET] button on the indoor unit to turn the air conditioner ON.
2. Point the remote control at the indoor unit.
3. Push and hold [CHECK] button on the Remote Control by the tip of the
pencil. "00" will be shown on the display (Picture
4. Press [MODE] during pushing [CHECK]. "B" will show on the display
and "00" will disappear and the air conditioner will turn OFF. The Remote
Control B is memorized (Picture
).
Note : 1. Repeat above step to reset Remote Control to be A.
2. Remote Control A have not "A" display.
3. Default setting of Remote Control from factory is A.
Earth line
Earth line
Connecting cable
Power cord
Earth line
Earth line
Connecting cable
Power cord

OTHERS

• Check the flare nut connections
for the gas leak with a gas leak
detector or soap water.
).
RAS-077, 107,
Model
137SKV Series
Power source
Maximum running current
Plug socket & fuse rating
Power cord
H07RN-F or 60245 IEC66 (1.5 mm
CAUTION
• Wrong wiring connection may cause some electrical parts burn out.
• Be sure to comply with local cords on running the wire from indoor unit
to outdoor unit (size of wire and wiring method, etc.).
• Every wire must be connected firmly.
• This installation fuse (16A) must be used for the power supply line of
this air conditioner.
• If incorrect or incomplete wiring is carried out, it will cause an ignition or
smoke.
• Prepare the power supply for exclusive use with the air conditioner.
• This product can be connected to the mains.
Connection to fixed wiring: A switch which disconnects all poles and
has a contact separation of at least 3 mm must be incorporated in the
fixed wiring.
NOTE
: Connecting cable
• Wire type : More than H07RN-F or 60245 IEC66 (1.0 mm

Test Operation

To switch the TEST RUN (COOL)
mode, press [RESET] button for
10 seconds. (The beeper will make
a short beep.)

Auto Restart Setting

This product is designed so that, after a power failure, it can restart automatically
in the same operating mode as before the power failure.
Information
The product was shipped with Auto Restart function in the off position.
Turn it on as required.
How to set the Auto Restart
1. Press and hold the [RESET] button on the indoor unit for 3 seconds to
set the operation. (3 beep sound and OPERATION lamp blink 5 time/sec
for 5 seconds)
2. Press and hold the [RESET] button on the indoor unit for 3 seconds to
cancel the operation. (3 beep sound but OPERATION lamp does not
blink)
• In case of ON timer or OFF timer are set, AUTO RESTART
OPERATION does not activate.
7
RAS-167SKV
Series
50Hz, 220 – 240 V Single phase
60Hz, 220 – 230 V Single phase
8A
10A
10A
16A
2
or more)
2
or more)
RESET button