PRODUCT INTRODUCTION
This product is a wireless interconnected photoelectric
smoke & heat detector, hereinafter called detector.
With a unique structure design and an intelligent MCU
to process photoelectric signals, it is provided with
dust-proof, mothproof, anti-light interference and other
functions, ensuring the detector stability from design
basis. Meanwhile, this detector could be wireless
interconnected with group detectors or wireless network
with alarm system. Once a detector is triggered, it will
send out wireless alarm signals to trigger the other
interconnected detectors or alarm system,suitable for
all kinds of installation environments and enhancing
users perceptionof alarm signal. It reacts very quick to
visible smoke released by smoldering fire and flaming
fire. When the environmental temperature over 57°C or
detects the
concentration of
smoke density reaches the
given alarm level, the detector LED flashes red and
buzzer gives out alarm sounds. It is suitable for fire
alarm in houses, factories, shopping malls, hotels,
restaurants, office buildings, teaching buildings, banks,
libraries, warehouses, etc..
PRODUCT PROFILE
OPERATING PRINCIPLE
This detector adopts the principle of smoke particles reflecting
infrared lights. The main circuit includes a MCU processing
part, an infrared emission part and an infrared reception part.
The emission and reception diodes are placed in the optical
maze chamber which can shield the interference of outside
stray lights, but will not influence smoke entering into the
detector. On smokeless conditions, the received infrared lights
are very weak. When smoke entering, due to scattering effects ,
the received light signals increase. When smoke density
accumulates up and reach the alarm threshold of the MCU, the
detector will blink its alarm indicator, give out strident alarm
sound and send out wireless alarm signal to trigger the other
interconnected detectors or alarm system.
User Manual for Wireless Interconnected Smoke & Heat Detector
POWER INDICATOR (AC type)
HEAT SENSOR
BUZZER
TEST & HUSH BUTTON
ALARM INDICATOR
FEATURES
●
Adopts MCU Auto-Processing Technology
●
Wireless Interconnected & Wireless Network Function
●
Test & Hush Button
●
Malfunction Auto-Check
●
Auto Reset After Trigger
● Smoke + Heat Dual Sensor
●
Sound & Flash Alarm / LED Indicating Alarm
●
SMT Manufacture Technology, Reliable Stability
●
Dust-proof, Moth-proof, Anti White Light Interference
●
Anti-RF Interference (20V/m-1GHz)
TECHNICAL PARAMETERS
Operating voltage:
①
9V battery (DC TYPE)
②
AC220V / 110V with 9V backup battery (AC TYPE)
Static current: < 50uA
Alarm current: < 45mA
Battery life: use lithium battery for about 1 year
Smoke sensitivity: 2.06%ft ±1.3%ft
Power indication: Green LED constant ON (AC TYPE)
Alarm indication: LED flashes in Red
≥
Alarm sound:
85dB/3m
Wireless interconnection frequency: 315/433MHz
Wireless transmitting distance: 200m (open area)
Code form: 1527/2262 optional
Operating temperature:-10
Φ
Dimension:
128* 38mm
Execution standard: GB4715-2005, EN14604, UL217
㎡
Detecting area: 80
at 6-12m installation height;
㎡
at installation height <6m.
60
INSTALLATION
1. Avoid installations in places with stagnating smoke, heavy
dust, heavy water mist, heavy oil mist, great humidity (>95%)
and high wind speed (>5m/s).
2. Insert the battery into battery cabinet with proper position.
3. Connect the AC power supply, red wire to L, black wire to N.
.
4. The center of detection ceiling area is recommended. Fix
the bracket base in proper position with screws. Crossing the
AC wire through bracket (AC TYPE).
5. Hang the detector
1
M207-2EVer1.0
≤ %RH)
°C~ +50°C ( 95
Need help?
Do you have a question about the HM-620PHW-AC and is the answer not in the manual?
Questions and answers