YAMABISHI ALS Series Instruction Manual page 14

On-line uninterruptible power supply

Advertisement

Problem
 
UPS no reaction while AC
is connected
 
UPS no reaction while AC
is connected, yet DC starts
after pushing power on/off
switch
 
UPS goes into DC mode
connected to AC
 
UPS still in bypass mode
after de-green mode
function
 
Keys on front panel don't
work
 
Press FUNCTION key in
AC mode, but the UPS goes
back to AC mode within
less than 10 seconds
 
Fault LED lit
 
Battery cannot provide
normal back up power
when there is no AC input
 
Causes
 
No AC input
 
UPS fault
 
Battery damaged
 
Input / output sensor fault
No AC input
 
UPS fault
 
AC voltage or frequency
abnormal
UPS AC detecting circuit
fails
 
UPS still in POWER OFF
status
 
UPS is proceeding
controlling process
 
Key damaged
 
Internal battery
deteriorated
 
UPS abnormal
 
Output load abnormal or
short circuited
 
Internal battery
deteriorated
 
Batteries not fully charged
Battery charger damaged
Solutions
Check AC power
 
Call for service
 
Call service to replace batteries
Call for service
 
Check AC power
 
Call for service
 
Check AC power
 
Call for service
 
Press power on/off key,
Buzzer sound once and the UPS
Become normal
 
Wait for a while to operate the UPS
Call for service
 
Call service to replace batteries
 
Call for service
 
Check load
 
Call service to replace batteries
 
Charge the battery
 
Replace charger and charge the
battery if necessary
 
 
 
 
 
 