weed instrument EOTec 2000 Installation Instructions page 2

Fiber optics optical module

Advertisement

Operational Settings
Use a small screwdriver to press on the latches
(indentations) at the top and bottom of the
housing. Slide the housing open.
The transmit optical power level default jumper
position setting is "H" (High). Select position "L"
(Low) only in overdriving (short fiber) conditions.
Jumper Locations
Each module of the modem must be configured
based on the network topology to be used. This
is accomplished by positioning a single jumper in
each module.
Standard (Point-to-Point, Daisy Chain, Star):
Electrical Module
Optical Modules (as added)
Self-Healing Ring (Fiber Media Redundancy):
Refer to Self-Healing Ring Installation
Instructions for proper jumper settings.
Repeater (Multiple Optical or Electrical Modules):
st
1
Module
Additional Modules (as added) 1,2,3,4
Additionally, each Optical Module must be
configured for the protocol being used. This is
accomplished by positioning a single jumper (J4).
DeviceNet
Profibus-DP
Profibus-DP Self-Healing Ring only PR
ControlNet Self-Healing Ring only
All remaining protocols
(Future expansion - undefined)
Close the housing by sliding it back together until
both the top and bottom latches "click" into place.
DIN Rail Mounting
Installation on DIN rail:
Place the top lip of the module's DIN rail mounting
channel onto the DIN rail. Push the lower portion
of the module towards the mounting surface until it
"clicks" and locks into place.
modules together such that the module sides are
touching ensuring a good connection of the
integrated BUS interconnection at the rear of the
modules. Install End Clamps (Model 2A09) to both
sides of the module bundle to prevent accidental
unplugging of the BUS interconnections. The End
Clamps also provide convenient screw terminals
for connecting the DIN rail to Protective Earth (PE)
ground.
Removal from DIN rail:
Remove the End Clamps from the module bundle.
Disconnect the BUS interconnections by sliding the
modules at least 1/2" apart from each other on the
DIN rail. Insert a screwdriver into the rectangular
hole in the metal mounting latch at the bottom of
the module.
Pushing up on the screwdriver's
handle causes the latch to move downward and
disengages it from the DIN rail. Tilt the module up
and lift it off of the DIN rail.
M
1,2,3,4
M
D
P
CR
E
LED Indicators
F
RX (Receive Optical Activity Indicator):
Amber - On or blinking with activity
TX (Transmit Optical Activity Indicator):
Green - On or blinking with activity
Mounting:
Weight:
Power Requirements:
Firmly slide the
Data Rates:
Optical Wavelength:
Fiber Compatibility:
Optical Connections:
Optical Dynamic Range
(utilizing fiber size)
9/125µm:
Important Note for
DeviceNet Only:
Operating Conditions
Temperature:
Relative Humidity: 0 to 95%
Flammability:
Hazardous Locations:
Notice: This model is not recommended for use
with the ControlNet protocol.
Specifications
35mm DIN Rail
< 9 oz (250g)
7.5 to 9.5Vdc @ 200mA
Supplied from any
EOTec 2000 Power
Supply via the integrated
BUS interconnections
9.6K to 12Mbps
1300nm, LED
5 to 10µm Optical Core,
Single-Mode
ST* Compatible
16dB
When using the 2E46
with DeviceNet module,
2C21, a minimum of 6dB
of loss in each fiber link
is required to prevent
over-drive conditions.
-40 to 85° C
(non-condensing)
UL 94V-0
Class I, Division 2,
Groups A, B, C & D, T4