(Heating requirements) for operation of heat pump • Sensor for second circuit • Platform to be set up in GGW / AGWGlycol protector • Fault indicating module (via SMS, Fax oder E-Mail) Material: GGW Glycol protector stainless 1.4301 in 1,5 mm or...
The condensation pan must be earthed. • Alterations and modifications to our product and its components are prohibited and can lead to failure or malfunction. • Do not operate GGW / AGW Gycol protector and components in areas with a high risk of damage. Specified minimum clearances are to be observed. • Safe operation of Protector and components can only be guaranteed for properly assembled devices and use as intended by the manu- •...
Page 5
GGW / AGW Glycol protector - Assembly instructions Recycling Disposal and packaging All products are carefully packaged to withstand transport damage. Please recycle all packaging material according to your countries waste management guide- lines. Warranty Warranty conditions are outlined in our „Allgemeine...
Contents of delivery GGW / AGW Glycol protector connecting screws ½", 3 per connection level screw nut ½“, 3 per connection level Assembly parts for pan according to drawing washer, Note: 6 per connection level Check delivery for completeness 1 safety valve with actuator...
Page 7
GGW / AGW Glycol protector - Assembly instructions Installation instruction GGW / AGW Glycol protector When choosing the appropriate size make sure all water hazarduous components can be fitted within the GGW /AGW Glycol pro- tector. Make sure the oil separator is not Note: covered by the unit and rain water can re- ach the pan.
Page 8
Align first part of pan vertically with outer edge of supporting structure. Assembling the pans is illustrated in drawings. Note position of separators. upended side Assembly Place second part of pan into first part as per drawing. Follow the same procedure with remaining parts. Make sure not to bend material. Ölprotektor.de...
Page 9
GGW / AGW Glycol protector - Assembly instructions Note: Make sure pan is resting firmly on supporting structure and oberserve drying time of loctite. Connecting Connect all parts with connecting screws. Use loctite to secure threads. Place washer onto thread and put screw through drilled hole.
Page 10
Platform Observe drawing. Seal exterior of plat- Apply an oil and water repellant sealing form with oil and water repellent material compound to the underside of the plat- (e.g. Silicone) form (e.g. Silicone). Position platform in protector. Hinweis: If the pan is accidently damaged when drilling, perform a pressure test for 24 hours to ensure leak tightness.
Page 11
GGW / AGW Glycol protector - Assembly instructions We can supply you with a copper adapter which includes a Schrader-Valve to be sol- dered into place. Please take note to re- move the Schrader-Valve during soldering. Screw pressure sensor onto existing or newly attached test port. Pressure sen- sor to be tightened with max 30 NM to avoid damage.
Page 12
Switch box / controle module pressure sensor platform protective cover (per safety valve) switch box (controle module) The control module is monitoring the Gly- The LED display ticker „Druckabfall“ (pres- col pressure. It is fitted with a push-but- sure drop) indicates a leak. The green ton to check operation. Pressure fluctua- push-button will close the valves for an tions are monitored and assessed.
Page 13
GGW / AGW Glycol protector - Assembly instructions Operation Different levels of configuration are accessed combinations. User-level is sufficient for device operation. All other configuration levels are secured with a PIN. Activate User-level by pushing Note: PGM-Key twice. Arrow-key will move cursor to parameter to be adjusted.
Circuit diagram of GGW / AGW Glycol protector- switch box / control module terminal row 3 terminal row 1 optional on number x expandable contact ¾ 0-10 bar <85 % open terminal row 2 optional on number x expandable contact ½...
GGW / AGW Glycol protector - Assembly instructions Connection plan Note: Make sure the display is clearly visible when mounting the control module. For any questions regarding assembly, implementation or service please contact our service telephone at: +49 5921 71347 - 0.
Page 16
Please note that different detergents dis- solve oil in water. The GGW / AGW glycol protector must be rinsed with water un- til no detergent is left in the GGW / AGW glycol protector if such cleaning has been used.
Page 17
GGW / AGW Glycol protector - Assembly instructions Leakage Check the GGW / AGW Glycol protector if a leakage is detected. Collected water of the GGW / AGW Glycol protector must be dis- posed properly. For this purpose a ¾"...