S&P CADB HE ECOWATT Series Manual page 7

Table of Contents

Advertisement

Vertical models
The models size 4 to 33 are supplied with support feet, while the models size 45 to 100 are supplied
with a perimetral bed. This bed must be in contact with the ground or with a fl at surface. It is es-
sential that the weight of the equipment is distributed between all points of support to prevent unit
deformation.
The installer must make sure that the ceiling structure and the securing elements can bear the
weight of the unit, taking into account that it is a dynamic load.
Models 04 to 33
Models 45, 60 and 100
Horizontal models of sizes 45 and 60
IMPORTANT!
Particularities in the installation of horizontal versions LH and RH
For a correct evacuation of condensation generated into the heat exchanger, it is necessary to ins-
tall the unit with a minimum slope of 3º to the side where the extraction fan is placed:
Model
Weight (kg)
4
139
8
175
12
182
16
227
21
325
33
412
Model
Weight (kg)
45
577
60
710
100
842