Terminal Block; Electrical Specifications - Delta Electronics IFD9506 Instruction Sheet

Ethernet communication module
Hide thumbs Also See for IFD9506:
Table of Contents

Advertisement

Available languages

Available languages

RS-485 Connector
Interface
Transmission method
Transmission speed
Communication format
Communication protocol
RS-232 Connector
Interface
Transmission method
Transmission speed
Communication format
Communication protocol
Transmission cable

Terminal Block

Interface
Transmission method
Transmission distance
Transmission speed
Communication format
Communication protocol Modbus

Electrical Specifications

Power voltage
Power consumption
Insulation voltage
Weight
Environment
Noise immunity
Operation/storage
Vibration/shock
immunity
Certificates
RJ-11
RS-485
110, 150, 300, 600, 1,200, 2,400, 4,800, 9,600, 19,200, 38,400, 57,600,
115,200
Stop bit: 1,2 Parity bit: None, Odd, Even Data bit: 7,8 ASCII/RTU
Modbus, User Define
Mini Dim
RS-232
110, 150, 300, 600, 1,200, 2,400, 4,800, 9,600, 19,200, 38,400, 57,600,
115,200
Stop bit: 1,2 Parity bit: None, Odd, Even Data bit: 7,8 ASCII/RTU
Modbus, Delta Configuration, User Define
DVPACAB215 / DVPACAB230 / DVPACAB2A30
Feed-through terminal 10PIN
RS-485
1,200m
110, 150, 300, 600, 1,200, 2,400, 4,800, 9,600, 19,200, 38,400, 57,600,
115,200
Stop bit: 1,2 Parity bit: None, Odd, Even Data bit: 7,8 ASCII/RTU
24V DC (-15% ~ 20%) supplied by feed-through terminal
3W
500V
140g
ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge
EFT (IEC 61131-2, IEC 61000-4-4): Power Line:±2KV, Digital Input: ±2KV,
Communication I/O: ±2KV
RS (IEC 61131-2, IEC 61000-4-3): 80MHz ~ 1GHz, 10V/m. 1.4GHz ~ 2.0GHz,
10V/m
Conducted Susceptibility Test (EN61000-4-6, IEC61131-2 9.10): 150KHz ~
80MHz, 3V/m
Surge Test (Biwave IEC61132-2, IEC61000-4-5):
Power line 0.5KV DM, Ethernet 0.5KV CM, RS-485 0.5KV CM
Operation: 0ºC ~ 55ºC (temperature), 50 ~ 95% (humidity), pollution degree 2
Storage: -25ºC ~ 70ºC (temperature), 5 ~ 95% (humidity)
International standards: IEC61131-2, IEC68-2-6 (TEST Fc)/IEC61131-2 & IEC
68-2-27(TEST Ea)