END SUCTION PUMPS
3801 3804
Model 3801
INSTALLATION AND
OPERATION MANUAL
pentair.com
A-03-327 (09/27/19)
AURORA
*
Model 3804
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the AURORA 3801 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Pentair AURORA 3801

  • Page 1 AURORA END SUCTION PUMPS 3801 3804 Model 3801 Model 3804 INSTALLATION AND OPERATION MANUAL pentair.com A-03-327 (09/27/19)
  • Page 2: Table Of Contents

    TABLE OF CONTENTS: SECTION .........................................PAGE General Information ....................................3 Transport and Storage .................................... 4 Product Description ....................................5 Pump Installation ....................................6-12 Pump Operation ....................................13-15 Pump Maintenance and Service ..............................16-20 Troubleshooting Guide ..................................21-22 Assembly Exploded View ................................. 23-24 Part List ........................................
  • Page 3: General Information

    This manual contains important information for the safe use of Isolate the pump from any fluid in the system and then Pentair Aurora* 3800 End Suction Pumps. Read this manual completely drain any remaining fluid from the pump casing before proceeding with before using this product.
  • Page 4: Transport And Storage

    • DO NOT turn on the electrical supply to the pump until all the Figure 1A plumbing connections and commissioning procedure have been Lifting of Pentair Aurora* 3804 pump assembly Figure 1A completed. Lifting of 3804 pump assembly •...
  • Page 5: Product Description

    Clean all parts of dirt, packing materials, and other foreign matter. Clean all non-coated machined surfaces. If the pump is to be installed • Pentair Aurora* 3801 close coupled immediately, then clean all coated machined surfaces too. Remove • Pentair Aurora 3804 frame mounted any rust spots found on the machined surfaces with a fine emery cloth.
  • Page 6: Pump Installation

    PUMP INSTALLATION INSTALLATION DISCHARGE PIPING Pump Location • Pentair Aurora* 3800 End Suction pump must be installed GATE VALVE horizontally. CHECK VALVE • The pump should be located as close to the liquid source as DISCHARGE possible so that the suction line can be short and direct.
  • Page 7 NOTICE: The pump base must be set level to avoid any mechanical difficulties with the pump or motor. Pentair Aurora* 3804 pump was properly aligned, if supplied with a motor, at the factory. However, since the pump base is flexible, it may spring and twist during shipment.
  • Page 8 PUMP INSTALLATION LONG EXCESSIVE Piping and Connections DISCHARGE UNSUPPORTED NUMBER OF PIPING ELBOWS Inlet and outlet piping should be anchored, supported, and restrained near the pump to avoid application of forces and moments to the pump in excess. In calculating forces and moments, the weights of the pipe, internal thrust, contained fluid and insulation, as well as thermal expansion and contraction, should be considered.
  • Page 9 PUMP INSTALLATION nozzle, but if it is unavoidable, they should be installed in a vertical SUCTION position. Elbows installed in any position at the suction nozzle have ECCENTRIC a tendency to distribute the liquid unevenly in the impeller chamber, DISCHARGE TAPERED POCKET REDUCER...
  • Page 10 The recommended pipe diameter can a flooded suction condition exists and a gate valve is required to shut off be obtained from your nearest Pentair Aurora* authorized distributor or the liquid supply for pump inspection and maintenance. The gate valve Customer Service.
  • Page 11 PUMP INSTALLATION Air Vent Valves BELLOWS TYPE DISCHARGE Vent valves are installed at the high points in the pump casing to allow EXPANSION JOINT air or vapor to escape. These valves are used to release trapped air from the pump casing during priming and when pump becomes air bound. See Figure 25 shown below.
  • Page 12 PUMP INSTALLATION To check angular alignment, insert a feeler gauge or taper gauge at any Pipe Alignment four places 90° apart around the coupling halves. Insert shims under the Proper piping alignment is essential before connection is made. Piping driver feet until the same reading is obtained at all four check points. alignment should never be achieved by force, as this could produce The pump and driver will then be in angular alignment.
  • Page 13: Pump Operation

    PUMP OPERATION DISCHARGE COMMISSIONING, START-UP, OPERATION, AND SHUTDOWN AIR POCKET SUCTION Lubrication In dry locations, each bearing will need lubrication at least after every 4,000 hours of running time or 6 to 12 months, whichever is more frequent. In wet locations (exposed to dripping water, to the weather INCORRECT or to heavy condensation found in unheated or poorly ventilated DECREASER...
  • Page 14 PUMP OPERATION slowly until a steady stream of liquid is observed flowing from the air vent. After your pump is operating, it is recommended that the air vent valve or plug be opened again to ensure that all air has been expelled from the pump casing.
  • Page 15 PUMP OPERATION DISCHARGE SPINDLE SUCTION AIR VENT PRESSURE LINE INLET STEAM INLET FROM PUMP LIQUID SUPPLY PRIMING INDUCTOR STEAM AND AIR DISCHARGE NOZZLE Figure 39 Figure 37 Figure 37 Inductor priming Figure 39 Ejector cutaway (Ejector cutaway) Inductor priming Vacuum Pumps SHAFT SEALING SETTINGS AND ADJUSTMENTS Rotary or reciprocating pumps are frequently used as vacuum pumps.
  • Page 16: Pump Maintenance And Service

    PUMP MAINTENANCE AND SERVICE Operation MAINTENANCE AND SERVICE The following points must be ensured before starting the pump: Schedule 1. The current supply agrees with the voltage and frequency on the Preventive maintenance and routine check-ups may prevent the pump motor nameplate.
  • Page 17 8-10 hours, which is the break-in EXCEPT 3550009644 4761255644 period for seal. During this operation the mechanical seal would ‘seat’ 6x8x9.5 properly. Pentair Aurora* 3800 pumps are supplied with type 21 mechanical seal. FLEXIBLE CUP 3550008644 4761256644 6x8x9.5 3550009644 4761256644...
  • Page 18 5. For Pentair Aurora 3804 pumps, remove the coupling guard. coupling bolts and grub screws and sequence of their tightening are 6. For Pentair Aurora 3804 pumps, loosen the set screws in both mentioned in the following section for replacement procedure of coupling halves and slide each half back as far as possible on its mechanical seals.
  • Page 19 If only mechanical seal is to be replaced, stop at this point and proceed to step 1 under section titled “Installation of the Mechanical Figure 44 Seal – 3801/3804 pumps”. Otherwise continue for Pentair Aurora* 3804 complete pump disassembly. A-03-327 (09/27/19)
  • Page 20 15. Tighten volute cap screws (#5) per torque chart (see Table 4 on Page 21. Thoroughly clean the shaft (#55), removing any oil or dirt. 18). 16. For Pentair Aurora 3804 pumps, install foot support cap screws Inspection (#62) Once the pumping unit is disassembled, component parts should be 17.
  • Page 21: Troubleshooting Guide

    TROUBLESHOOTING GUIDE THE FOLLOWING IS A LIST OF COMMON PROBLEMS AND THEIR PROBABLE CAUSES. Symptoms Possible causes Possible remedies Check and ensure correct voltage at motor terminals Speed too low Check if rotating elements freely rotate Check motor rotation with direction arrow on casing Wrong direction of rotation Ensure correct motor wiring Ensure all air is vented, and pump is adequately primed...
  • Page 22 Rubbing or binding of rotating elements stationary components Note: The pump delivered may not be fitted with all the components mentioned in the troubleshooting guide. For further troubleshooting assistance, contact Pentair Aurora Customer Service or your nearest Pentair Aurora authorized distributor. A-03-327 (09/27/19)
  • Page 23: Assembly Exploded View

    ASSEMBLY EXPLODED VIEW PENTAIR AURORA* MODEL 3801 CLOSE COUPLED CONFIGURATION Figure 45 Figure 45 Pentair Aurora Model 3801, close coupled configuration A-03-327 (98/27/19)
  • Page 24 ASSEMBLY EXPLODED VIEW PENTAIR AURORA* MODEL 3804 FRAME MOUNTED CONFIGURATION Figure 46 Figure 46 Pentair Aurora Model 3804, frame mounted configuration A-03-327 (09/27/19)
  • Page 25: Part List

    PART LIST PENTAIR AURORA* 3801 AND 3804 Reference: Figure 45, 46 (Exploded Views) ITEM NO. DESCRIPTION Pipe plug 4A/B. Cap screw Cap screw washer Cap screw Casing Gasket Impeller screw Impeller washer Impeller gasket Impeller seal O-ring Impeller Impeller key...
  • Page 26: Standard Limited Warranty

    STANDARD LIMITED WARRANTY WARRANTY Seller warrants equipment (and its component parts) of its own manufacture against defects in materials and workmanship under normal use and service for one (1) year from the date of installation or start-up, or for eighteen (18) months after the date of shipment, whichever occurs first. Seller does not warrant accessories or components that are not manufactured by Seller;...
  • Page 27 *For a detailed list of where Pentair trademarks are registered, please visit www.pentair.com/en/registrations.html. Pentair trademarks and logos are owned by Pentair PLC. or its affiliates. Third party registered and unregistered trademarks and logos are the property of their respective owners. Because we are continuously improving our products and services, Pentair reserves the right to change specifications without prior notice.