Make:
Type
Available models:
CONNECTION DAIGRAM:
The communication terminals (RS485) are located at the bottom of the inverter. And there are
two connection terminals on the configuration circuit board: ++ - - terminal blocks.
Connection Steps
Please unscrew the RS485 terminal as shown in A part of Figure 1.
Please make the connections from the Terminal Block to Holmium Dlog as mentioned in Table
Connect the cables from Holmium Dlog to communication port of inverter as shown below
DLOG
Input
Reverse
Suppl
Supply
Kstar Pin No.
1
2
3
4
KSTAR
Solar on Grid string inverter
KSG-30K,KSG-36K,KSG-50K,KSG-60K
Figure 1: KSTAR string inverter communication port and connections
>
^
O
K
GSM
Powe Net
wor St
at RF
Syn
Figure 2: Connection of Dlog with KSTAR RS485 chip
Kstar Assignment
(A) R/T+
(A) R/T+
(B) R/T-
(B) R/T-
Table 1: Kstar chip connection with Holmium Dlog
Holmium
Pin No.
RS485 IN
3
RS485 OUT
RS485 IN
4
RS485 OUT
1
Holmium
Assignment
D+
D-

Advertisement

loading

Summary of Contents for KStar KSG-30K

  • Page 1 The communication terminals (RS485) are located at the bottom of the inverter. And there are two connection terminals on the configuration circuit board: ++ - - terminal blocks. Figure 1: KSTAR string inverter communication port and connections Connection Steps ➢...
  • Page 2: Setting The Baud Rate

    Multiple Inverter Pin 2 & 4 of Inv-1 is connected to Pin 1 & 3 of next inverter in Daisy Chain. When two or more inverters are in parallel communication, 2P DIP switch beside RS485 of the last one should be “ON”. Or else, it may cause communication interruption. That 2P DIP switch is on, means connecting a 120Ω...
  • Page 3: Setting The Inverter Id

    ENTER button. Press ESC button to cancel choice and return back the setup interface. NOTE: The above details are mentioned in the Installation & Operation Manual for Kstar KSG 30K/36K/50K/(60K- HV)/60K on Page 28.
  • Page 4 HOLMIUM WORKING: installation guide Ensure correct connections as detailed in the Connection Diagram: Insert SIM card: Insert the sim card in data logger. It must not be a JIO SIM CARD. Required internet data for uninterrupted operation is 1GB/Month 2G/3G preferred. Plug antenna: Connect the antenna in data logger.
  • Page 5: Important Links

    PORTAL DETAILS IMPORTANT LINKS Please login to MODBUS Connection Guide for inverters: //www.holmiumtechnologies.com// using given credentials. PORTAL DETAILS 2. Remote monitoring LOGIN address: Please login to //www.holmiumtechnologies.com// using given credentials. Contact us: www.holmiumtechnologies.com||info@holmiumtechnologies.com||8890586586...

This manual is also suitable for: