Automatic testing and reclosing rccb device

Advertisement

CDAxxxRA, CFAxxxRA
Teknisk data / Technical characteristics
Distribution system
Rated operational voltage Ue
In
Im n
Type
10000 A (gL 63 A In = 25 - 40 A, gL 80 A In = 63 A)
Off-load absorbed power
Reclosing absorbed power
Dissipated power at In
Insulation voltage to earth
Rated impulse withstand
voltage Uimp
Blocking threshold Rdo
2/4P 8 kΩ IΔn 30 mA, 2,5 kΩ IΔn 300 mA
Reset threshold Rd
2/4P 16 kΩ IΔn 30 mA, 5 kΩ IΔn 300 mA
Time of reclosing
Time of automatic testing
Width
Operating temperature
Auxiliary contact
Imax
Imin
Installation
230 Vv
L
N
OFF
N
L
LOAD
2 Nm
400 V v
L L L N
L L L N
1
Jordfelsbrytare med automatisk
s
återställning och självtestfunktion
Automatic testing and reclosing
z
RCCB device
TT - TN
230 - 400 Vac
25 - 40 - 63 A
30 - 300 mA
A [IR]
4 (cos = 0,2)
41 (cos = 0,5)
2P 2,2 W (25 A), 4P 3,5 W (25 A), 6 W
(40 A), 12 W (63 A)
2500 Vac for 1 min.
4 kV
< 10 s
< 7 s
5 - 7 Modules
-25°C ➡ +60°C, daily average ≤ 35°C
5 ÷ 230 Vac / dc
100 mA (cos  = 1),
0,6 mA / AC12
Ingripande är endast tillåten närenhet är
isolerad och enheten har varit avstängd
(kåpa förflyttas åt höger och hävarm
åtkomlig) /
Intervention is only permitted when the
unit is isolated and the device has been
switched off (slide moved to the right and
lever accessible)
2 Nm
AUX
≤ 2,5 mm
230 V v
L N
OK
OK
OK
OK
L N
Mått / Dimensions
2P
90
17,8
3
0,4 Nm
2
≤ 35mm
400 V v
L L
L L
Apparaten får endast installeras av
behörig elektriker enligt i landet gällande
installationsnormer.
This device is to be installed only by a
professional electrician fitter according to
local applicable installation standards.
4P
124,8
17,8
Anslutning / Connexion
2P
L
N
T
Last / Load
Last / Load
L
T
L
N
Nej / No
4P
L1
L2
L3
N
2
Last / Load
Last / Load
L1
L2
L3
N
Nej / No
7,4
f+
ARD
N
N
f+
ARD
N
f+
ARD
N
N
f+
ARD
N
6LE001872Ab

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the CDA RA Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for hager CDA RA Series

  • Page 1 Jordfelsbrytare med automatisk återställning och självtestfunktion Automatic testing and reclosing RCCB device Apparaten får endast installeras av behörig elektriker enligt i landet gällande installationsnormer. This device is to be installed only by a professional electrician fitter according to CDAxxxRA, CFAxxxRA local applicable installation standards.
  • Page 2 Test av automatisk återställning / Automatic reset test 230 Vv Clack ! LED ON Vid uppstart, lös ut brytaren genom att föra in en skruvmejsel genom hålet på luckan och trycka på testknappen. Om återställningscykel inte kunde slutföras korrekt, kontrollera installationens jord, som måste vara: CDAxxxRA 2/4P 30mA Rd≥...
  • Page 3 LED indikering / LED signals contact röd / gul - grön / green red / yellow OFF MODE (t >15 min) Fel på produkt / Device fault gul/ yellow Fel på produkt / Device fault gul / yellow Jordfelsbrytar skydd KO / Residual current protection KO Jordfelsbrytar skydd KO / Residual current protection KO...
  • Page 4 Explanation of defect must be included when returning goods. Hager Electro S.A.S., Boulevard d'Europe, B.P. 3, 67215 OBERNAI CEDEX, France - www.hager.com Hager 07.17 OCOM 128938...