6.1.7
Procedure
Q.series
Gantner Instruments GmbH
unit, e.g. mV/V measured value and mV/V displayed value.
You can then define the unit displayed for the measurement in
the column Format/balance column.
8. Save the settings with File > Send to module or click on

Specifying digital inputs/outputs

In order to set parameters you should be connected to the mod-
ule and have called the configuration program ICP 100. For con-
figuration select the module you want from the list of modules.
Then carry out all the module settings in the window that is then
displayed.
All module signals are defined as variables. Therefore, for the
entry activate the tab Variable definition.
Fig. 6-10
Dialog w ith configuration for digital input and output.
1. Click in the column Type of the first row (V1 = Variable 1) or
mark the row (click on V1) and use Variable definition >
Type.
2. Select Digit. input or Digit. output.
The column Wiring diagram shows you the pin assignment.
With more than one input the first inputs are also always
occupied first (first Plug 1, then Plug 2, etc.). Check for cor-
rect connection.
3. Click in the column Variable name and allocate a name iden-
tifying the signal. Note that in the PDO mapping only the first
four characters of the name are used; the channels are then
e.g. Vari_0, Vari_1, etc.
4. At a digital output click in the column Type of and specify
whether you want to use the output as Status indicator, Sta-
tus field or Process output.
Process output: The output monitors a module signal and
changes the output level under certain conditions. Click in the
column Other and specify the type of alarm monitoring.
6
Configuration → Configuration via ICP 100
.
95