Technical Specifications; Installation; Recommended Handling Procedure; Location And Positioning - Immergas Inoxstor 200 Installation, Usage And Maintenance Instructions

Pre-plumbed water heater for use with audax heat pumps
Table of Contents

Advertisement

2.3

TECHNICAL SPECIFICATIONS

Hydraulic performance
Storage tank unit capacity
Domestic hot water side maximum pressure
DHW side maximum temperature
Maximum coil pressure
Central heating side maximum temperature
Empty storage tank unit weight
Full storage tank unit weight
Heat dispersion
Psbsol
3.

INSTALLATION

Carefully read and observe all instructions in the following sections. Failure to follow these instructions many
invalidate the warranty and / or lead to an unsafe situation.
3.1

RECOMMENDED HANDLING PROCEDURE

Keep the Inoxstor in its original packaging until time of installation to prevent damage. Do not store it outdoors or in any
damp location. Take care when lifting or moving the Inoxstor. Ensure that all local manual handling regulations are followed
to avoid the risk of injury.
Store the Inoxstor in a vertical orientation, resting on its base. Never lay the Inoxstor down horizontally. Take care not to dam-
age the manifold or any attached valves, devices , wiring or electronics when moving the Inoxstor.
3.2

LOCATION AND POSITIONING

The Inoxstor must be installed in a dry location, indoors. It is not suitable for outdoor use. The Inoxstor must be installed in a
vertical orientation.
Check the load bearing capacity of any floors or walls to ensure that they can support the weight of the water heater when
filled to capacity. Refer to section 2.3 for full weight of the water heater.
Enough space must be left at the top and sides of the unit for pipe connections and access to the safety controls and valves.
Refer to sections 2.1 and 2.2 to determine a suitable position for the heater. Allow sufficient clearance for access and service.
Ensure the location allows the Immersion to be removed if required.
Refer to sections 3.3 and 3.4 to determine which valves and accessories are required. Plumb the valves as shown in the rele-
vant diagrams. An isolating valve must be fitted on the cold water supply to the heater.
DO NOT install the water heater where the unit may freeze.
DO NOT mount the Inoxstor horizontally. It will not function correctly.
The Inoxstor must not be installed in a location where water leakage is likely to cause damage. If it is necessary
to install the Inoxstor in such a location (e.g. an attic or higher floor of a building), a 'tanked', waterproof chamber
fitted with a drain should be created to ensure that any potential leaks from the product and associated fittings or
pipes are contained and drained away safely.
Inoxstor Pre-Plumbed Water Heater
l
207
bar
8
°C
99
bar
6
°C
90
kg
65
kg
279
kW h / 24 h 1.95
W/K
1.81
Installation, Usage and Maintenance Instructions
Exchange surface
m2
Coil capacity
l
Exchange power
kW
Primary fluid flowrate
l/h
Primary fluid T delta
°C
Useful reintegration
kW
power
Upper coil Lower Coil
0.72
1.3
4.1
7.5
32
52
1630
2950
17
15
26.3
34.3
5