4.4.7

Weather compensation curve

The weather compensation curve is set by parameter 46 with permissible values from 30 to 50. The
default value is 45. This means that the Solis will automatically adjust the flow temperature as the
ambient temperature drops, to a maximum flow temperature of 45°C. See graphs above.
Likewise, if cooling has been enabled by the factory, the flow temperature will automatically decrease as
the temperature increases as defined in parameter 45.
decreasing the value moves the curve down the temperature scale. Permissible values are -15 to15.
The default value is 0.

4.5 System Protection and Error Codes

In the unlikely event of a fault, the controller will show an error code consisting of a letter (E,F or P) and a
number. The controller will also show a code is encounters circumstances such that it needs to shut down
for safety reasons. The most common codes are:
Code
Meaning
E1
Compressor overheat or
discharge high temp protection
E2
Outdoor air temp sensor error
E3
Pipe or return air temp sensor
error
E4
AC return water temp sensor
error
E5
AC leaving water temp sensor
error
E6
DHW temp sensor error
E7
Solar water temp sensor error
E8
fan coil high temp protection
E9
System anti freeze twice
EA
DHW anti freeze twice
EB
Indoor refrigerant pipe sensor
error
EC
Water source inlet water sensor
error
ED
Water source leaving temp
sensor
EE
Water source anti freeze
Dated 17/09/19 V1.2
Increasing the value moves the curve up,
LED2
Remark
Red flashing
Decided by outdoor unit
Flashes 3 times
Outdoor air temp sensor open circuit or short circuit
Flashes 6 times
(1 )temp sensor open circuit or short circuit
(2) suck sensor open or short circuit
Red flashing
Stops compressor when running AC
Red flashing
Stops compressor when running AC
Red flashing
Stops compressor when running AC
As normal
Won't stop compressor
Red flashing
Water source anti freeze protection
Red flashing
Stops compressor
Red flashing
Stops compressor
No flashing
Temp sensor open circuit or short circuit
No flashing
Temp sensor open circuit or short circuit
No flashing
Temp sensor open circuit or short circuit
No flashing
1.Water source heat exchange not efficient or water
23 of 39
ESP-HC-DHW 11DC
ESP-HC-DHW 17DC