Mitsubishi Electric EMU4-D65 Instruction Manual page 5

For energy measuring unit
Hide thumbs Also See for EMU4-D65:
Table of Contents

Advertisement

Screen
7(1) Setup the demand time
EMU4-BM1-MB
7(1)-1.
(1) In 7-1, push the ▲ or ▼ key, and move the cursor to the "6 Demand".
[Measure]
(2) Push the
4 DISP.Mode
(3) 7(1)-2 will be displayed.
5 MEA.Mode
6
Demand
7(1)-2.
(1) Push the ▲ or ▼ key, and move the cursor to the A(Current).
[Demand]
(2) Push the + or - key, and change the demand time value.
A :
2min
(3) Push the ▲ or ▼ key, and move the cursor to the W(Electric power).
W : 2min
(4) Push the + or - key, and change the demand time value.
(5) Push the
(6) 7(1)-1 will be displayed.
7(2) Setup the demand time
EMU4-LG1-MB
7(2)-1
In 7(2)-1, push the ▲ or ▼ key, and move the cursor to the "6 Demand".
(1)
[Measure]
(2) Push the
4 DISP.Mode
(3) 7(2)-2 will be displayed.
5 MEA.Mode
6
Demand
7(2)-2
(1) Push the + or - key, and change the Io/Ior demand time value.
[Demand]
(2) Push the
Io/Ior:
5min
(3) 7(2)-1 will be displayed.
8 Setup the electric energy equivalent rate
8-1.
(1) In 8-1, push the ▲ or ▼ key, and move the cursor to the "7 CONV.Wh"
[Measure]
(2) Push the
5 MEA.Mode
(3) 8-2 will be displayed.
6 Demand
7
CONV.Wh
8-2.
(1) Push the ▲ ▼ + - key, and change the "CONV.Rate" value and unit.
[CONV.Rate]
(2) Push the
1.000
(3) Transition to the following screen by the setting wiring type.
[Unit]
2 circuit measurement → To 8-3
Non
[1]
non-2 circuit measurement → To 8-1
8-3.
(1) In a similar way as 8-2, change the "CONV.Rate" value and unit of the second circuit.
[CONV.Rate]
(2) Push the
1.000
(3) 8-1 will be displayed.
[Unit]
Non
[2]
9 Setup the the current cut-off rate
9-1.
(1) In 9-1,push the
[Measure]
(2) Push the
6 Demand
(3) 9-2 will be displayed.
7 CONV.Wh
8
A Cut-off
9-2.
(1) Push the + or - key, and change the set value.
[A Cut-off]
(2) Push the
0.05%
(3) Transition to the following screen by the setting wiring type.
2 circuit measurement → To 9-3
[1]
non-2 circuit measurement → To 9-1
9-3.
(1) In a similar way as 9-2, change the "A Cut-off" value of the second circuit.
[A Cut-off]
(2) Push the
0.05%
(3) 9-1 will be displayed.
[2]
10 Setup the Simple measurement
10-1.
(1) In 10-1, push the ▲ or ▼ key, and move the cursor to the "9 SimpleMEA".
[Measure]
(2) Push the
7 CONV.Wh
(3) 10-2 will be displayed.
8 A Cut-off
9
SimpleMEA
10-2.
(1) Push the + or - key, and select SimpleMEA ([On]/[Off]).
[SimpleMEA]
(2) Push the
Off
(3) Transition to the following screen by the setting SimpleMEA ([On]/[Off])
[On] setting → To 10-3
[Off] setting → To 10-1
10-3.
(1) Push the ▲ ▼ + - key, and change the power factor value in the SimpleMEA.
[FP Set]
(2) Push the
1.000
(3) Transition to the following screen by the setting wiring type.
2 circuit measurement → To 10-4
[1]
non-2 circuit measurement → To 10-1
10-4.
(1) In a similar way as 10-3, change the power factor value of the second circuit.
[FP Set]
(2) Push the
1.000
(3) 10-1 will be displayed.
[2]
11 Setup the Ior difference conversion
11-1.
(1) In 11-1, push the ▲ or ▼ key , and move the cursor to the "10 DIF.CONV".
[Measure]
(2) Push the
8 A Cut-off
(3) 11-2 will be displayed.
9 SimpleMEA
10
DIF.CONV
11-2.
(1) Push the + or - key, and select the Ior difference converted value([On]/[Off])
[DIF.CONV ]
(2) Push the
(3) Transition to the following screen by the setting DIF.CONV ([On]/[Off]).
Off
[On] setting → To 11-3
[Off] setting → To 11-1
Operation
EMU4-HM1-MB
EMU4-A2
/ Phase
key.
/ Phase
key , and confirm the setting value.
/ Phase
key and
/ Phase
key, and confirm the setting value.
All models except for EMU4-LG1-MB
/ Phase
key.
/ Phase
key , and confirm the setting value.
/ Phase
key, and confirm the setting value.
All models except for EMU4-LG1-MB, EMU4-PX4 and EMU4-AX4
▲ or ▼ key , and move the cursor to the "8 A Cut -off".
/ Phase
key.
key , and confirm the setting value.
/ Phase
/ Phase
key, and confirm the setting value.
All models except for EMU4-LG1-MB, EMU4-PX4 and EMU4-AX4
/ Phase
key.
/ Phase
key, and confirm the setting value.
/ Phase
key,and confirm the setting value.
/ Phase
key, and confirm the setting value.
EMU4-LG1-MB only
/ Phase
key.
/ Phase
key, and confirm the setting value.
EMU4-VA2
- 5 -
Note
[Demand]:0sec⇔10sec⇔20sec⇔30sec⇔40sec⇔50sec⇔
1min ⇔ 2min ⇔ 3min ⇔ 4min ⇔ 5min ⇔ 6min ⇔ 7min ⇔
8min ⇔ 9min ⇔ 10min ⇔ 11min ⇔ 12min ⇔ 13min ⇔
14min⇔ 15min⇔20min⇔25min⇔30min⇔
[Demand]:0sec⇔5min⇔6min⇔7min⇔8min⇔9min⇔10min⇔
11min ⇔ 12min ⇔ 13min ⇔ 14min ⇔ 15min ⇔ 20min ⇔
25min⇔30min⇔
[CONV.Rate]:0.001~10000(1.000
[Unit]:
Non⇔Wh⇔kWh⇔MWh⇔J⇔m
min⇔hour⇔piece⇔set⇔g⇔kg⇔t⇔¥⇔$⇔
[A Cut-off]:0.1~50.0% (0.5)
A cut-off rate... represent as the ratio of cut-off current to
rated current.
※Measured value is 0A if it is less than the cut -off current.
[SimpleMEA]:Off⇔On⇔
SimpleMEA...The value set in the electric power and the power
factor as the fixed value. By measuring the current
only, and calculating the values of the measurement
elements.
[FP Set]:-0.001~1.000~0.000
[DIF.CONV]:Off⇔On⇔
DIF.CONV...To calculate the amount of change from the
Ior difference converted value.
2
3
⇔m
⇔L⇔kL⇔sec⇔