B.E.G. WAVE-PIR-120/277 Installation Instructions

Vacancy sensor switch

Advertisement

Quick Links

INSTALLATION INSTRUCTIONS
WAVE-PIR-120/277
VACANCY SENSOR
Part Number: 97334
SPECIFICATIONS
Voltage .................................................................... 120/277VAC, 60Hz
Incandescent ............................................................................ 800W
Fluorescent/Ballast/LED.............. 800VA@120VAC /1600VA@277VAC
Motor .............................................................................................1/4HP
Time Delay.....................................................................15Sec to 30Mins
Light Level...................................................................... 30 Lux--Daylight
Operation Temperature....................................................... 32°F--131°F
DESCRIPTION
The passive infrared sensors work by detecting the difference between
heat emitted from the human body in motion and the background space.
If no motion is detected after the set time delay, the load turned off
automatically. The sensor switch has one relay ( equal to single pole
switch), also includes Ambient Light Level Sensor.
Coverage Area
The coverage range of the sensor switch is specified and illustrated
in Figure 1. Large objects and some transparent barriers like glass
windows will obstruct the sensors' view and prevent detection, causing
the light to turn off eventhough someone is still in the detection area.
Top View
20'
10'
Best: 320 sq.ft.
10'
Regular: 800 sq.ft.
20'
Maximum: 1200 sq.ft.
5'
4'
20'
- 01-
WARNING:
SWITCH
INSTALLATION
1. Connect lead wires as WIRING DIAGRAM (see Figure 2): Black lead to
Line(Hot), Red lead to Load wire, Green lead to Ground.
Wiring Diagram:
2. Gently position wires in wall box, attach sensor switch to the box.
3. Mount device "TOP"up.
4. Restore power at circuit breaker or fuse, wait
5. Remove the small cover plate. (illustrated as Figure 3. )
6. Locate the adjustment knobs on the control panel to perform test and
adjustment.(illustrated as Figure 3. )
7. Replace the small cover plate after testing and adjustment.
8. Attach the wallplate.
Figure 1
40'
Turn off the circuit breaker before installation.
Ground wire is required.
Indoor use only.
Do not exceed electrical ratings.
Neutral
White
Hot
Load
Load
Red
Black
Ground
Green
Figure 2
three
minutes.
Figure 3
-02-
ADJUSTMENT
10 Min
2
3
5
20
Min
Min
30
TEST
Min
1
4
TIME
RANGE
OFF VAC VAC
OFF VAC VAC
Band switch prescription.
Mode
Position
Description
Circuit is permanently opened
Left
OFF
(switched off)
Vacancy Mode: Manual On only,
VAC
Center
automatic Off after set time delay.
Vacancy Mode: Manual On only,
VAC
Right
automatic Off after set time delay.
Time Delay knob
Default position: 15 Seconds (Test mode)
Adjustable: from 15 Seconds to 30 Minutes (clockwise)
Sensor Sensitivity Range Knob
Default position: Center at 65%
Adjustable: 30% (Position 1) to 100% (Position 4)
Note: Turn toward right for greater room space.
Turn toward left to avoid false alert in smaller room and near
the door way or heat source.
Ambient Light Level Adjustment
After Initial Run (3 minutes), set the Band Switch to VAC, press and
hold the Manual ON/OFF Button for 6 seconds until the Load turns on,
release the button within the next 4 seconds, the Load will turn off and
stay off or a maximum 10 seconds. The Load will turn on again (2
seconds) and then Off. It confirms that the present light level becomes
-03-
Mounting Yoke
Fresnel Lens
LED Indicator
Control Panel Cover
(Push-button)
Figure 4
React to the push-button
Manually toggles
On / Off the load.
Manually toggles
On / Off the load.
Manually toggles
On / Off the load.

Advertisement

loading

Summary of Contents for B.E.G. WAVE-PIR-120/277

  • Page 1 INSTALLATION INSTRUCTIONS ADJUSTMENT WAVE-PIR-120/277 WARNING: Turn off the circuit breaker before installation. Ground wire is required. VACANCY SENSOR Mounting Yoke Indoor use only. Do not exceed electrical ratings. SWITCH Fresnel Lens LED Indicator INSTALLATION Control Panel Cover (Push-button) 1. Connect lead wires as WIRING DIAGRAM (see Figure 2): Black lead to Part Number: 97334 Line(Hot), Red lead to Load wire, Green lead to Ground.
  • Page 2 INSTALLATION INSTRUCTIONS The Load is out of control (frequently flashing) the set Ambient Light Level. 1. It can take up to three minutes for initial run. For technical support please call (770) OPERATION 2. Check the wiring connections, especially the Ground Wiring .

This manual is also suitable for:

97334