B.E.G. WAVE-PIR-120/277-N Installation Instructions

Vacancy sensor switch

Advertisement

Quick Links

INSTALLATION INSTRUCTIONS

WAVE-PIR-120/277-N
VACANCY SENSOR
Part Number: 97332
SPECIFICATIONS
Voltage ....................................................................120/277VAC, 60Hz
Incandescent .............................................................................800W
Fluorescent/Ballast/LED...............800VA@120VAC /1600VA@277VAC
Motor ......................................................................................... 1/4HP
Time Delay................................................................. 15Sec to 30Mins
Light Level.................................................................... 30 Lux--Daylight
Operation Temperature...................................................... 32 F--131 F
DESCRIPTION
The passive infrared sensors work by detecting the difference between
heat emitted from the human body in motion and the background space.
If no motion is detected for the set time delay, the load turned off
automatically. The sensor switch has one relay (equal to single pole
switch), also includes Ambient Light Level Sensor.
Coverage Area
The coverage range of the sensor switch is specified and illustrated
in Figure 1. Large objects and some transparent barriers like glass
windows will obstruct the sensors' view and prevent detection, causing
the light to turn off eventhough someone is still in the detection area.
Top View
20'
10'
Best: 320 sq.ft.
10'
Regular: 800 sq.ft.
20'
Maximum: 1200 sq.ft.
5'
4'
20'
- 01-
WARNING:
SWITCH
INSTALLATION
1. Connect lead wires as WIRING DIAGRAM (see Figure 2): Black lead
to Hot wire, Red lead to Load wire, White lead to Neutral wire, and
Green lead to Ground wire.
Wiring Diagram:
NOTE: DO NOT connect RED & WHITE wires on device together! It
may cause short circuit!
2. Gently position wires in wall box, attach sensor switch to the box.
3. Mount device "TOP"up.
4. Restore power at circuit breaker or fuse, wait
5. Remove the small cover plate. (Illustrated as Figure 3. )
6. Locate the adjustment knobs on the control panel to perform test
and adjustment.(Illustrated as Figure 3. )
7. Replace the small cover plate after testing and adjustment.
8. Attach the wallplate.
Figure 1
40'
Turn off the circuit breaker before installation;
In door use only;
Do not exceed electrical ratings.
Neutral
White
Hot
Load
Load
Red
Black
Neutral
Ground
White
Green
Figure 2
one
minute.
Figure 3
-02-
ADJUSTMENT
10
20
2
Min
Min
3
2
30
TEST
Min
1
4
1
TIME
RANGE
LIGHT
OFF VAC VAC
OFF VAC VAC
Band switch prescription.
Mode
Position
Description
Circuit is permanently opened.
OFF
Left
(switched off)
Vacancy Mode: Manual On only,
Center
VAC
Automatic Off after set time delay.
Vacancy Mode: Manual On only,
Right
VAC
Automatic Off after set time delay.
Time Delay knob
Default position: 15 Seconds (Test mode)
Adjustable: from 15 Seconds to 30 Minutes (clockwise)
Sensor Sensitivity Range Knob
Default position: Center at 65%
Adjustable: 30% (Position 1) to 100% (Position 4)
Note: Turn toward right for greater room space.
Turn toward left to avoid false alert in smaller room and near the
door way or heat source.
Ambient Light Level Knob
Default position: Daylight (100% at position 4)
Adjustable: Daylight to 30Lux (Counter clockwise)
Note: to avoid wasting energy by turn-on the light under daylight.
-03-
Mounting Yoke
Fresnel Lens
LED Indicator
Control Panel Cover
(Push Button)
3
4
Figure 4
Function of the push-button
None
Manually toggles
On / Off the load.
Manually toggles
On/Off the load.

Advertisement

loading
Need help?

Need help?

Do you have a question about the WAVE-PIR-120/277-N and is the answer not in the manual?

Questions and answers

Summary of Contents for B.E.G. WAVE-PIR-120/277-N

  • Page 1: Installation Instructions

    INSTALLATION INSTRUCTIONS WAVE-PIR-120/277-N ADJUSTMENT WARNING: Turn off the circuit breaker before installation; Mounting Yoke In door use only; VACANCY SENSOR Do not exceed electrical ratings. Fresnel Lens SWITCH LED Indicator INSTALLATION Control Panel Cover (Push Button) Part Number: 97332 1. Connect lead wires as WIRING DIAGRAM (see Figure 2): Black lead...
  • Page 2 The Load does not turn Off by any mode. 1. There can be up to a 30 minutes time delay after the last motion For WAVE-PIR-120/277-N, there is night NOTE : detected. To verify proper operation, turn the Time Delay Knob to 15s...