Mitsubishi Electric MELIPC MI5000 Series Programming Manual page 125

Vxworks
Hide thumbs Also See for MELIPC MI5000 Series:
Table of Contents

Advertisement

*1
Error code
Description
Decimal
Hexadec
imal
■Registry open error
-34
FFDEH
Opening parameter files in the registry failed.
-35
FFDDH
■Registry read error
Reading parameter files from the registry failed.
■Registry write error
-36
FFDCH
Writing parameter files to the registry failed.
-37
FFDBH
■Communications initialization error
Initializing the setting for communication failed.
■Close error
-42
FFD6H
Communications cannot be closed.
-43
FFD5H
■ROM operation error
A TC setting value was written to the CPU module during ROM
operation.
■MELSEC data link function service error
-52
FFCCH
MELSEC data link function service is disabled.
-53
FFCBH
■Timeout value error
The specified timeout value is out of range.
■I/O number error
-54
FFCAH
The specified I/O number is out of range.
-55
FFC9H
■Logical station number error
The specified logical station number is out of range.
■Target CPU error
-56
FFC8H
The specified target CPU is out of range.
-71
FFB9H
■Remote device station access error
Failed to access the buffer memory of the remote device station.
■Connection destination CPU error
-80
FFB0H
The connection destination CPU is not an RCPU.
-4097 to
EFFFH to
Refer to the following manuals.
MELSEC iQ-R CC-Link IE Controller Network User's Manual (Application)
-8192
E000H
 MELSEC-Q CC-Link IE Controller Network Reference Manual
-8193 to
DFFFH to
Refer to the following manuals.
MELSEC iQ-R CC-Link IE Field Network User's Manual (Application)
-12288
D000H
 MELSEC-Q CC-Link IE Field Network Master/Local Module User's Manual
MELSEC-L CC-Link IE Field Network Master/Local Module User's Manual
-16385 to
BFFFH to
Refer to the following manuals.
MELSEC iQ-R CC-Link System Master/Local Module User's Manual (Application)
-20480
B000H
 MELSEC-Q CC-Link System Master/Local Module User's Manual
MELSEC-L CC-Link System Master/Local Module User's Manual
*1 When the function of which the return value is a long-type, the value will be eight digits in hexadecimal.
Corrective action
Check if the access target is correctly set with MI Configurator.
• Check if the access target is correctly set with MI
Configurator.
• Check if the setting for the channel number is enabled.
• After checking the parameters with MI Configurator again and
writing them, reset the MELIPC or turn the power supply OFF
to ON.
• Check if the standard ROM has already been shutdown.
• Reset the MELIPC, or turn the power OFF and ON.
• Retry.
• The memory may be insufficient. End other running tasks.
• Check the available memory capacity.
• Check if the MELIPC is running normally.
• Reset the MELIPC, or turn the power OFF and ON.
• Retry.
• Check if the MELIPC is running normally.
• Reset the MELIPC, or turn the power OFF and ON.
Change the TC setting value during RAM operation.
Enable the MELSEC data link function service using MI
Configurator.
Check the specified time out value.
Check the specified I/O number.
Check the specified logical station number.
Check the specified target CPU.
• Check whether the target station is the remote device station
of the CC-Link IE Field Network.
• Check the network number and station number.
• Check whether the offset or the offset plus the read/write byte
size is within range of the buffer memory of the target station.
Connect an RCPU.
Appendix 1 Function error codes
A
APPX
123