WIRING
Power Supply / Power Wiring Specifications
Outdoor unit(s) and indoor units / heat recovery units must be provided power from separate breakers. For detailed information, see the Multi
V Outdoor Unit Engineering and Installation Manuals on www.lghvac.com.
Indoor Units (and Heat Recovery Units)
• Indoor units (and heat recovery units) require 1Ø, 208-230V, 60Hz power, but each unit draws minimal power.
• Where permitted by NEC and local codes, multiple indoor units (and heat recovery units) can be powered from a single breaker.
• Service switches typically must be installed for each indoor unit (and each heat recovery unit).
• Ground each indoor unit (and heat recovery unit) separately to a solid earth ground source per NEC and local code requirements.