GENERAL INSTALLATION GUIDELINES
Installing in an Area Exposed to Unconditioned Air
In some installation applications, areas (floors, walls) in some rooms may be exposed to unconditioned air. The room may be above or next
to an unheated garage or storeroom. To counter this condition:
• Verify that carpet is or will be installed (carpet may increase the temperature by three [3] degrees)
• Add insulation between the floor joists
• Install radiant heat or another type of heating system to the floor.
Required Clearances for Cassette Indoor Units
See the figure below for required clearance distances around a typical installed Cassette indoor unit.
Figure 8: Selecting the Best Location / Minimum Clearance Requirements — One-, Two-, and Four-Way Ceiling-Cassette Indoor Units.
* Four-Way TQ/TR Frames
1-3/16 ± 1/8
* Four-Way TN/TM Frames
19/32 ±1/8
* Two-Way TS Frames
13/16 ±1/8
30
Ceiling
Ceiling Tile
19-11/16
or more
"A"
One-Way: 70-7/8 to 129-15/16 inches
Two-Way: 70-7/8 to 129-15/16 inches
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
13/32
or more
39-3/8
or more
"A"
Floor
Four-Way <36,000 Btu/h: 70-7/8 to 141-23/32 inches
Four-Way >36,000 Btu/h: 70-7/8 to 165-11/32 inches
One-Way
Only: 7-7/8 or more
Ceiling Tile
19-11/16
11-13/16
or more
or less
Unit: Inch