Samsung MXD-K000PN Installation Manual page 6

Packaged doas kit
Table of Contents

Advertisement

Installing the packaged DOAS Kit
CAUTION
• You should switch off the power supply and disconnect the power cable.
(Abnormal operation of the product may occur due to the electric problem.)
3
Set the address of the Packaged DOAS Kit.
CN3
CN2
RED
BLK
Address switch for Packaged DOAS Kit
• SW1: Address switch, set the address within 0~F (0~15) (Address between each Packaged DOAS Kit should be set differently)
• SW4 #1: Option switch, which sets automatic/manual address setting when Packaged DOAS Kit and Fresh Access™
Packaged DOAS have been installed.
To set automatic/manual address setting, set as in the following table. (Default: automatic address setting)
(This function is only applicable when new communication upper level controller is connected.)
• SW4 #2 : Option Switch, which sets "BAS Control" when Packaged DOAS Kit and Fresh Access Packaged DOAS have been installed.
To set "No Set"/"Hold BAS Control", set as in the following table. (Default Hold BAS Control)
(This function is only applicable when Packaged DOAS ALC Controller is connected .)
Hold BAS Control: Monitors the setting value of Occupancy Control Option of ALC Controller and keeps it on
2-BAS Control continuously.
No Set: No Set Occupancy Control Option
Purpose - Use when you want to control local schedule or 24/7 control and so on according to administrator's
purpose via the touch controller.
ON
SW4
Manual address
SW5
• When connecting a 485 communication cable between the Packaged DOAS Kit and the DMS, be sure to match the
polarity. If the polarity does not match, communication is impossible.
CAUTION
• Both distances from the Packaged DOAS Kit to the DMS must be within 3,280 feet.
• You should switch off the power supply before installation.
• The wiring should be installed in accordance with electric wiring regulations and should be placed inside the wall so
that users cannot touch them.
6 English
SOL Packaged DOAS Kit 북미향 IM_EN_DB68-08395A-00.indd 6
SW 4
SW 5
ON
OFF
SW 1
1
2
1
2
1
OFF (default)
Automatic address
No Set
No function
Rotate the arrow using a
flathead screwdriver until it
points to the addresss you
want to set.
2
ON
OFF (default)
Hold BAS Control
SW4
SW5
2
1
2
1
2019-03-28 오후 3:36:57