ALC Controller

Setting the ALC Controller for packaged DOAS Kit

1
Change the port jumper settings from the current settings (ARC-156, default) to the new settings (RS485).
2
Set the communication settings:
A. Power off the ALC controller.
B. Set the tens digit of the rotary switch to "0" and the unit digit to "1."
NOTe
Packaged DOAS Kit has 1 for its Modbus address.
10's
0
SW5
The tens digit is set to 0.
C. Set the Dip switch settings for baud rate, protocols, ports, and more: set the dip switch to "off off off off off off off on."
ON
D. Power on the ALC controller.
SOL Packaged DOAS Kit 북미향 IM_EN_DB68-08395A-00.indd 11
1's
0
SW4
The unit digit is set to 1.
Modbus
Baud - set to 9600
BAS - Port1
IP Address
Enhanced access port
Current settings
New settings
(ARC-156)
(RS485)
English