Advertisement

Quick Links

ENMET
PO Box 979
Ann Arbor, MI 48106-0979
www.enmet.com
CP-60
O
M
PERATION AND
AINTENANCE
M
ANUAL
Manual Part Number
80003-501
MCN-423, 07/15/09

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the CP-60 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for ENMET CP-60

  • Page 1 ENMET PO Box 979 Ann Arbor, MI 48106-0979 www.enmet.com CP-60 PERATION AND AINTENANCE ANUAL Manual Part Number 80003-501 MCN-423, 07/15/09...
  • Page 2: Table Of Contents

    1.3 Check Order ................................1 1.4 Serial Numbers................................ 1 2.0 Instrument Features ..............................2 2.1 CP-60 Exterior Features ............................2 2.2 Display CP-60 Front Panel Features ........................2 2.3 Circuit Board Features ............................3 3.0 Installation .................................. 4 3.1 Mounting of Instrument ............................4 3.3 Power Supply ................................
  • Page 3 Figure 1: CP-60 External Features ..............................2 Figure 2: CP-60 Interior Features................................ 3 Figure 3: CP-60 Mounting Dimensions .............................. 4 Figure 5: CP-60 Relay, Input and Output Terminals .......................... 6 Figure 6: CP-60 Operational Display ..............................8 Figure 7: CP-60 Operation Menu Flow Chart ............................. 9 Figure 8: CP-60 Maintenance Menu Flow Chart ..........................
  • Page 4: Introduction

    CP-60 ENMET 1.0 Introduction The CP-60 control panel is capable of monitoring from 1 to 3 remote sensors. Some features of the monitoring system are as follows: continuous LCD menu driven operational and maintenance controls menu driven calibration procedure audio and visual alarms indicate unsafe conditions...
  • Page 5: Instrument Features

    Flanges with holes for mounting the enclosure to a vertical surface. 2.2 Display CP-60 Front Panel Features The display panel, shown in Figure 1, is viewed through the clear front cover of the enclosure, and is accessed by opening the cover.
  • Page 6: Circuit Board Features

    Alarm Channel 1 Fault 4–20mA Transmitter 1 Alarm Channel 2 4–20mA Transmitter 2 Horn Terminal Channel 3 4–20mA Transmitter 3 Fuse Holder Hole Plugs Audio Alarm Ground Screw J21 Power Input Terminal J23 Strain Relief Figure 2: CP-60 Interior Features...
  • Page 7: Installation

    The holes in the flanges are 0.31 inch in diameter and form a 6 x 10.75 inch rectangle. See Figure 3. It is recommended to use #8 drywall anchors and screws for mounting the CP-60 to a drywall/sheetrock surface. Mounting Holes 0.31”...
  • Page 8: Sensor/Transmitter Connection

    If you have a question involving the location of a unit or sensor, please contact your distributor or ENMET personnel. A technician will analyze the question and recommend a location.
  • Page 9: Outputs

    4-20mA Input Channel 1 J18 Connector Transmitter 2 4-20mA Input Channel 2 J19 Connector Transmitter 3 4-20mA Input Channel 3 Fuse Holder FH2 Ground Screw Press Power Input, Terminal J23 L-Line N-Neutral Figure 5: CP-60 Relay, Input and Output Terminals...
  • Page 10: Relay Contacts

    Wiring requirements are the same as for the relays. 3.4.4 Digital Outputs The RS232 & RS485 connections are used for firmware updates and digital communications. The CP-60 is designed to operate as a modbus slave. Contact the ENMET for further information on wiring for the digital outputs.
  • Page 11: Operation

    The Alarm 1 differential value is the delay of the CP-60 staying in alarm condition until after the measured reading has returned past the alarm point by the differential value. Example: If the alarm point is V 19.5 and the differential is 2, the CP-60 will go into alarm at 19.5 and stay in alarm until the reading has risen above 21.5.
  • Page 12: Display

    Figure 7: CP-60 Operation Menu Flow Chart 4.7 Fault Indications Fault indication occurs: When a transmitter is not connected to an active channel of the CP-60. When a connected Sensor/Transmitter reading falls out side of its operation parameters (See sensor/transmitter manual).
  • Page 13: Maintenance

    : Never spray a cleaning solution on the surfaces of the CP-60. AUTION Clean the exterior of the CP-60 enclosure with a mild soap solution on a clean, damp cloth. Do not soak the cloth with solution so that moisture drips onto, or lingers on, external surfaces.
  • Page 14: Set 4 -20Ma Transmitter Scale

    CP-60 ENMET 5.2.1 Set 4 –20mA Transmitter Scale This section of the maintenance menu is for external sensor/transmitters. This function is normally performed at the factory and is not usually required in the field unless a new transmitter with a different range is installed.
  • Page 15: Set Alarm Points

    OPTION Note: The Alarm 1 differential value is the delay of the CP-60 staying in alarm condition until after the measured reading has returned past the alarm point by the differential value. Example: If the alarm set point is 19.5 and the differential is 2, the...
  • Page 16 CP-60 ENMET Example: Set Alarms Flow Chart Displays shown are factory default settings. Λ - Indicates alarm triggered on increasing value of reading Indicates alarm triggered on decreasing value of reading Indicates alarm is set for latching Indicates alarm is set for non-latching STD –...
  • Page 17: Set Alarm "Delay On

    The Table 2 below shows the default relay links for 3 channel system. Table 2: Default Relay Links Channel 1 Channel 2 Channel 3 Channel 4 Channel 4 Not Relay 1 Low Alarm Available in CP-60 Relay 2 Low Alarm Default Relay 3 Low Alarm programming of Relay 4 Spare...
  • Page 18: Failsafe Configuration

    5.2.5 Failsafe Configuration The CP-60 is factory set in a failsafe configuration. This means that if power is disconnected to the unit, or the relay fails to properly engage, it fails in such a way that it is in the alarm position. ENMET recommends leaving the relay in a failsafe configuration.
  • Page 19: Set New Password

    : Deactivated channels will not display or respond to connected sensor transmitters. AUTION A fault indication occurs when a transmitter is not connected to an active channel of the CP-60. To Activate or deactivate a channel of the CP-60: Enter the maintenance menu as described in Section 5.2 and press the switch until Exit maint menu appears.
  • Page 20: Technical Data And Specifications

    CP-60 ENMET 6.0 Technical Data and Specifications The technical data and specifications of the CP-60 instrument. Electrical Power 15 Amp fused branch circuit 100 – 240 V 0.9 A 50/60 Hz Board Mounted Fuse FH2, 0.630A, 5 x 20mm Storage and Transport Temperature: -20°...
  • Page 21: Warranty

    ENMET shall not be liable for any loss or damage caused by the improper use of the product. The purchaser indemnifies and saves harmless the company with respect to any loss or damages that may arise through the use by the purchaser or others of this equipment.
  • Page 22 734.761.1270 Fax 734.761.3220 Returning an Instrument for Repair ENMET instruments may be returned to the factory or any one of our Field Service Centers for regular repair service or calibration. The ENMET Repair Department and Field Service Centers also perform warranty service work.
  • Page 23 K UPS Account number: ________________________ K Federal Express: K Ground K Express Saver K P-1 K Standard K 2-Day Air K FedEx Account number: ________________________ Would you like ENMET to insure the return shipment? K No K Yes Insurance Amount: $_________________...

Table of Contents