Connecting the Power Converter to an AC Power Source

Connecting the Power Converter to an AC Power Source
The following instructions are provided for a qualified electrician to attach the AC power cord to the power
supply.
Caution
AC power sources must be dedicated AC branch circuits. Each branch circuit must be protected by a dedicated
two-pole circuit breaker.
Caution
Do not insert the power cord into the AC outlet until the process of wiring the line, neutral, and ground
connections has been completed.
To connect the AC power cord to the power converter, follow these steps:
Before you begin
To connect the power converter to an AC power source, you need an AC power cord. Power cord connector
types and standards vary by country. Power-cord wiring color codes also vary by country. You must to have
a qualified electrician select, prepare, and install the appropriate power cord to the power supply.
Note
Use copper conductors only, rated at a minimum temperature of 167°F (75°C).
Step 1
Remove the plastic cover from the input power terminals and set it aside.