''EASY LIGHT'' SERIES FOR NON-MAINTAINED/ΜΑΙΝΤΑΙΝΕD
TECHNICAL CHARACTERISTICS
OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
BATTERIES (Ni-Cd)
BATTERY PROTECTION
INDICATIONS - CONTROLS
CHARGING TIME
MINIMUM AUTONOMOUS DURATION
ILLUMINATION SOURCE
EMERGENCY ILLUMINATION
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
CONSTRUCTION MATERIALS
EXTERNAL DIMENSIONS
TYPICAL WEIGHT
GUARANTEE
Thank you for purchasing this product of
Olympia Electronics. A European manufacturer.
GENERAL
These luminaires are used indoors (ta 40 C)
where emergency light is needed.
Each luminaire must be permanently connected
to mains power supply.
In normal operation the battery is charging and
the 2 yellow LED's light in the screen.
In case of a mains power supply failure the
luminaire will light the led strip automatically in
emergency mode. When the mains power
supply is restored the device turns to normal
operation.
MAINTAINED / NON-MAINTAINED
OPERATION
There is an option to select the maintained or
non-maintained operation by placing the jumper
to the appropriate place according to step 8
(page 4).
INSTALLATION
To install the luminaire follow the installation
instructions οn page 4.
ΑΤΤΕΝΤΙΟΝ!!!
1. Operations for installation, maintainance or
testing must be done by authorized personel
only.
2. The device must be connected to the mains
power supply thru a fuse dependent by the total
amount of the line's power load.
Page 1 from 4
High Quality European based Manufacturers
EMERGENCY LUMINAIRES
GR-310/15L
3,6V/600mAh
90min
EN 60598-1, EN 60598-2-22, EN 55015, EN 61547, EN 61000-3-2, EN 61000-3-3
Bayblend FR3010, transparent polycarbonate
350 x 134 x 45 mm (CRV 362 x 134 x 58 mm)
655gr.
3. It is sugested to check every month the
indication LED for battery charging, and by
p u s h i n g t h e T E S T b u t t o n t o c h e c k t h e
emergency circuit. The led strip should: a) light
o
with bigger intensity as long as the TEST button
is pressed (maintained operation),
b) light as long as the TEST button is pressed
(non-maintained operation).
doesn't work as described above contact the
installer.
4. It is sugested to check every 6 months the
minimum autononous duration by disconnecting
the mains power supply. Count the time that the
led strip lights and in case of less time than the
minimum autonomous duration the battery must
b e r e p l a c e d . I f t h e m e a s u r e d t i m e i s
considerably less than the minimum autonomous
duration
or led strip replacement, these must be replaced
by parts of the same type, by the manufacturer
or by a competent person.
5. In case of inactive use for a period greater
than 2 months, disconnect the battery by pulling
out the battery's connector.
6. I s not allowed to discard batteries in to
220-240V AC/50-60Hz
3W /3VA
From overcharge and full discharge
Battery charging LED, TEST button
24h
15 white LED's
105lm
IP 40
o
0 to 40 C
Up to 95%
3 years (1 year for the battery)
contact the installer.
t i
common trash bins, they must be
discarded only
points. Do not incinerate.
GR-312/15L
3,6V/1,5Ah
180min
735gr.
If the luminaire
In case of battery
in battery recycling
923312017_09_003