Installation Of Out- Door Unit - LG AUUQ18GHT0 Installation Manual

Table of Contents

Advertisement

INSTALLATION OF OUTDOOR UNIT
Installation Places
- If an awning is built over the unit to prevent direct sunlight or rain exposure, make sure that
heat radiation from the condenser is not restricted.
- Ensure that the spaces indicated by arrows around front, back and side of the unit.
- Do not place animals and plants in the path of the warm air.
- Take the air conditioner weight into account and select a place where noise and vibration are
minimum.
- Select a place so that the warm air and noise from the air conditioner do not disturb neighbors.
Piping length and the elevation
Free Joint Single Outdoor
MODEL
CAPACITY
AUUQ18GHT0
18 kBtu/h
AUUW18GHT0
18 kBtu/h
AUUQ24GHT0
24 kBtu/h Ø 15.88(5/8) Ø 9.52(3/8)
AUUW24GHT0
AUUQ30GHT0
28 kBtu/h Ø 15.88(5/8) Ø 9.52(3/8)
AUUW30GHT0
AUUQ36GHT0
34 kBtu/h Ø 15.88(5/8) Ø 9.52(3/8)
AUUW36GHT0
AUUQ48GHT0
46 kBtu/h Ø 19.05(3/4) Ø 9.52(3/8)
AUUW48GHT0
AUUQ54GHT0
AUUW54GHT0
54 kBtu/h Ø 19.05(3/4) Ø 9.52(3/8)
AUUQ60GHT0
AUUW60GHT0
More than
300 mm
F e
n c e
o b
o r
s t a
c l e
s
Pipe Size
Gas
Liquid
Ø 12.7(1/2) Ø 6.35(1/4)
Ø 12.7(1/2) Ø 6.35(1/4)
INSTALLATION OF OUTDOOR UNIT
Unit : mm
More than
More than
More than
300 mm
300mm
300mm
More than 600 mm
More than 700 mm
Length A (m)
Standard
Max.
7.5
30
7.5
50
7.5
50
7.5
50
7.5
50
7.5
50
7.5
50
Additional
Elevation B (m)
Refrigerant
Standard
Max.
(g/m)
5
15
20
5
30
20
5
30
40
5
30
40
5
30
40
5
30
40
5
30
40
7