Carrier Weathermaster 48P2030-100 Controls, Start-Up, Operation, Service, And Troubleshooting page 182

Single package large rooftop units with comfortlink version 7.x controls
Table of Contents

Advertisement

ITEM
TEST
Service Test Mode
STOP
Local Machine Disable
S.STP
Soft Stop Request
FAN.F
Supply Fan Request
INDP
TEST INDEPENDENT OUTPUTS
HUM.R
Humidifier Relay
ALRM
Remote Alarm / Aux Relay
FANS
TEST FANS
F.MOD
Fan Test Automatic?
E.POS
Econo Damper Command Pos
S.FAN
Supply Fan Relay
S.VFD
Supply Fan VFD Speed
P.E.1
Power Exhaust Relay 1
E.VFD
Exhaust Fan VFD Speed
P.E.2
Power Exhaust Relay 2
BP1.C
BP 1 Command Position
BP2.C
BP 2 Command Position
CDF.1
Condenser Fan Output 1
CDF.2
Condenser Fan Output 2
CDF.3
Condenser Fan Output 3
CDF.4
Condenser Fan Output 4
ACT.C
CALIBRATE TEST-ACTUATORS
ECN.C
Economizer Act.Cmd.Pos.
EC.CL
Economizer Calibrate Cmd
ECN.A
Econ Act. Control Angle
EC2.C
Economzr 2 Act.Cmd.Pos.
E2.CL
Economzr 2 Calibrate Cmd
EC2.A
Econ2 Act. Control Angle
BP1.C
BP 1 Command Position
B1.CL
BP 1 Actuator Cal Cmd
BP1.A
BP Act.1 Control Angle
BP1.M
BP 1 Actuator Max Pos.
BP2.C
BP 2 Command Position
B2.CL
BP 2 Actuator Cal Cmd
BP2.A
BP Act.2 Control Angle
BP2.M
BP 2 Actuator Max Pos.
HTC.C
Ht.Coil Command Position
HT.CL
Heating Coil Act. Cal.Cmd
HTC.A
Heat Coil Act.Ctl.Angle
HMD.C
Humidifier Command Pos.
HM.CL
Humidifier Act. Cal.Cmd
HMD.A
Humidifier Act.Ctrl.Ang.
HMZR
TEST HUMIDIMIZER
RHV
HumidiMiZer 3-way Valve
C.EXV
Condenser EXV Position
B.EXV
Bypass EXV Position
C.CAL
Condenser EXV Calibrate
B.CAL
Bypass EXV Calibrate
COOL
TEST COOLING
E.POS
Econo Damper Command Pos
SP.SP
Static Pressure Setpoint
CL.ST
Requested Cool Stage
MLV
Minimum Load Valve Relay
A1
Compressor A1 Relay
A1.CP
Compressor A1 Capacity
A1.B1
Two Circuit Start A1,B1
A2
Compressor A2 Relay
A3
Compressor A3 Relay
B1
Compressor B1 Relay
B2
Compressor B2 Relay
B3
Compressor B3 Relay
RHV
HumidiMiZer 3-way Valve
C.EXV
Condenser EXV Position
B.EXV
Bypass EXV Position
HEAT
TEST HEATING
HT.ST
Requested Heat Stage
HT.1
Heat Relay 1
H1.CP
Modulating Heat Capacity
HT.2
Heat Relay 2
HT.3
Relay 3 W1 Gas Valve 2
HT.4
Relay 4 W2 Gas Valve 2
HT.5
Relay 5 W1 Gas Valve 3
HT.6
Relay 6 W2 Gas Valve 3
H.I.R
Heat Interlock Relay
HTC.C
Ht.Coil Command Position
APPENDIX A — LOCAL DISPLAY TABLES
Table B — MODE — SERVICE TEST
EXPANSION
ON/OFF
YES/NO
YES/NO
YES/NO
ON/OFF
ON/OFF
YES/NO
ON/OFF
0-100
ON/OFF
0-100
ON/OFF
0-100
0-100
ON/OFF
ON/OFF
ON/OFF
ON/OFF
0-100
YES/NO
read only
0-100
YES/NO
read only
0-100
YES/NO
read only
0-100
0-100
YES/NO
read only
0-100
0-100
YES/NO
read only
0-100
YES/NO
read only
Off/On
0 to 100
0 to 100
Off/On
Off/On
0-100
0-5
0-n
ON/OFF
ON/OFF
20-100
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
Off/On
0 to 100
0 to 100
0-n
ON/OFF
0-100
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
0-100
RANGE
UNITS
CCN POINT
MAN_CTRL
UNITSTOP
SOFTSTOP
SFANFORC
HUMR_TST
ALRM_TST
FANAUTO
%
ECONFANS
SFAN_TST
%
SFVFDTST
PE1_TST
%
EFVFDTST
PE2_TST
%
BLDPTST1
%
BLDPTST2
CDF1_TST
CDF2_TST
CDF3_TST
CDF4_TST
%
ECON1TST
ECONOCAL
ECONCANG
%
ECON2TST
ECON2CAL
ECN2CANG
%
BLDG1TST
BLDG1CAL
BP1_CANG
%
BP1SETMX
%
BLDG2TST
BLDG2CAL
BP2_CANG
%
BP2SETMX
%
HTCLACTC
HCOILCAL
HTCLCANG
%
HUMD_TST
HUMIDCAL
HUMDCANG
RHVH_TST
%
CEXVHTST
%
BEXVHTST
CEXV_CAL
BEXV_CAL
%
ECONCOOL
" H2O
SPSP_TST
CLST_TST
MLV_TST
CMPA1TST
A1CAPTST
CMPABTST
CMPA2TST
CMPA3TST
CMPB1TST
CMPB2TST
CMPB3TST
RHVH_TST
%
CEXVHTST
%
BEXVHTST
HTST_TST
HS1_TST
%
MGAS_TST
HS2_TST
HS3_TST
HS4_TST
HS5_TST
HS6_TST
HIR_TST
%
HTCLHEAT
182
WRITE STATUS
PAGE NO.
37
config
37
forcible
37
forcible
37
37
37
36,37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
36
37
37
37
37
37
37
37
37,38
37,38
37,38
37,38
37,38
37,38
37,38
37,38
37
37
37
37
37
37
37
37
37
37-38
37-38
37-38
37,39
37,39
37,39
37,39
37,39
37,39
37,39
37,39
37,39
37,39