11.0 Setup and configuration of the unit
1.
Replace the side panels of the unit, followed by the lid.
2.
Replace the fuses to the spurs supplying the unit and turn on the mains power.
3.
Check that the pump/s are receiving power (with the unit switched off) by lifting the float switches on
the pump/s.
4.
Switch the unit on; the screen will display a left to right start sequence, followed by the software release.
5.
A C0 will show on the display while the unit checks the environment and the connections. C0 will be present
for approximately 10-15 seconds.
6.
If the unit passes the initial config, a CC will be shown on the display and then the unit will restart and show
-- followed by On and then flip between the charging bars and the -- while the unit calculates the battery
percentage (this can take up to 3 minutes). Once the unit has calculated the battery percent, it will
stop displaying -- and show a figure from 0-99% depending on the state of the battery.
7.
If the unit fails to configure correctly (error code below) - switch the unit off, remove the fuses from the spurs,
remove the side panels and lid, redo the connections or set the configuration switches to the correct
positions and then replace the covers and turn the unit back on. If the issue still persists, please call
technical support on 0330 9000 999.
8.
If you are connecting an AlertMaxx2 or Rego, please refer to section 14.0 of this manual.
Code
C0
C1
C2
C3
C4
C5
C6
Config started.
No primary mains present. Check supply.
No secondary mains present. Check supply.
No battery connected. Connect battery.
Primary mains 'in' and pump 'out' swapped. Swap over wiring.
Secondary mains 'in' and pump 'out' swapped. Swap over wiring.
Pump switch in '1P', but 2 mains 'in' detected. Change switch to correct setting.
During initial configuration
9