2.6 SURE-SAVE Cooling Injection
(Optional: 125-750 scfm model)
Standard: Models with I-C Level 3 Controller
Dryers outfitted with the SURE-SAVE option automatically
protect the refrigeration compressor from damage due
to excessive inlet air temperatures. A temperature sensor
continually monitors the compressor operating
conditions. If the temperature exceeds standard design
conditions, the SURE-SAVE cooling injection valve
automatically redirects cooling energy back to the suction
side. This allows continued operation with an elevated
pressure dew point rather than initiate a high
temperature shutdown. To protect the dryer, high inlet
air temperature shutdown will occur if inlet air
temperature exceeds 140°F.
Vacuum
Fluorescent
Text Display
On
Switch
Off
Switch
Gauge
Temperature
LED's
I-Controller Level 3 - (Optional)
2.7 I-Controller Level 3 –
(Optional on 200-750 scfm models)
Dryers upgraded with the optional I-Controller Level 3
include text messaging on the Vacuum Fluorescent Text
Display (VFTD), Alert/Alarm condition display panel
warning lights, process diagram LED indicator lights,
Demand Operated Condensate Drains(s) and SURE-SAVE
Heat Reliever as standard features.
Programming, Start-up and, Operating Instructions
Dryers are pre-programmed in accordance with the
manufacturers recommendations. Programming details
are listed within Table 1.
NOTES:
a) Programming can be accomplished while dryer is in
either the ON or OFF mode.
b) The OPERATION sub-directory list automatically scrolls
sequentially every 3 seconds. Press the (ENTER) key
repeatedly to scroll manually.
Table 1
Operation Maintenance
Configuration
(view)
(view)
(programmable*) (factory
Dew Point
Hours
Gardner Denver
Temp (°F/°C)
to Service
IC3 Ver (xxx)
Ambient Temp
Total
*Set Language Eng., English
(°F/°C)
Hours
Spanish, French
Inlet Air Temp
(°F/°C)
HR:MIN:SEC
MO/DA/YR
Dryer
ON (OFF)
6
Drain LED
Alarm Light
Maintenance
Programming
Buttons
LED's
Unit Set Up
(programmable*) (factory
setting)
n/a
*Dew Point Set Pt
(50°F-95°F)
*Ambient Set Pt
( 95°F-122°F)
*Set Date
Current
*Inlet Air Set Pt
MO/DA/YR
(95°F-140°F)
*Set Time
Eastern
*Service Interval
HR:MIN:SEC
Standard
(0-4000 Hours)
*Set Temp
°F/°C
F
VFTD Text Viewing Instructions
1.
Press (Right-Arrow) or (Left-Arrow) to select from the
following Main Menu items: OPERATION,
MAINTENANCE, CONFIGURATION, UNIT SET UP
2.
Press the (ENTER) key to access the sub-directory of
the Main Menu item of your choice.
NOTE: Press (ENTER) repeatedly to sequence through the
sub-directory text displays listed in table 1.
Warning/
Light
Programming Instructions (CONFIGURATION or UNIT
Reset
SET UP modes only)
Compressor
Running Light
1.
Press (Right-Arrow) or (Left-Arrow) to select from the
Drain Push-
following Main Menu items: OPERATION,
to-Test
Power-on
MAINTENANCE, CONFIGURATION, UNIT SET UP
Light
2.
Press the (ENTER) key to access the sub-directory of
the Main Menu item of your choice.
Note: Press (ENTER) repeatedly to sequence through
the sub-directory text displays as listed in table 1.
3.
To reprogram your selection, press and release and/
or hold down the (+) or (-) key until you reach the
desired value
4.
Press (ENTER) to accept the new setting.
NOTES:
a) Display will automatically return to normal operating
mode 30 seconds after last key is depressed.
b) Programming automatically reverts back to prior
settings in 30 seconds if (ENTER) is not depressed.
Start-up Instructions - I-Controller Level 3 (Continued
from Section 2.2)
1.
Energize dryer.
A. Green POWER ON light will illuminate.
B. VFTD will read "GARDNER DENVER IC3 (version)"
Text display automatically sequences at 3 second
intervals in the following order:
a. AMBIENT AIR TEMP (°F or °C)
b. INLET AIR TEMP (°F or °C)
c. TIME/DATE (hours: minutes: seconds/month/
d. DRYER OFF or ON (status)
e. DEW POINT TEMP (°F or °C)
C. LEDs – The GREEN Thermometer LEDs on the
Process Diagram will illuminate when the
corresponding temperature point is shown in the
setting)
VFTD.
50°F/
10°C
2.
Depress Green (START) button.
105°F/
A. The Green "COMPRESSOR ON" panel light
41°C
and process diagram LED will illuminate.
105°F/
41°C
2000
NOTE: If dryer is started while "DRYER OFF" is displayed
Hours
within the VFTD, it will change to "DRYER ON" with the
next display rotation.
Left Arrow
Right Arrow
Enter
Programming Buttons
day/year)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Crn125Crn200Crn250Crn300Crn500Crn400 ... Show all

Table of Contents