SIZING

Determining dryer capacity at actual operating conditions
To determine the maximum inlet flow capacity of a dryer
at various operating conditions, multiply the rated capacity
from Table 1 by the multipliers shown in Table 2.
Example: How many scfm can an air-cooled 750 scfm
model handle when compressed air to be dried is at 200
psig and 100°F; ambient air temperature is 80°F; and a
38°F dew point temperature is desired?
Answer: 750 x 1.22 x 1.12 x 1.0 = 1,025 scfm.
TABLE 1
Rated capacity (scfm) and pressure drop @ 100 psig inlet
pressure, 100°F inlet temperature, and 100°F ambient
temperature
MODELS
125
150
Rated capacity 60 Hz
125
150
of air-cooled
50 Hz
104
125
models (scfm)
10
200
250
300
400
500
200
250
300
400
500
167
208
250
333
417
TABLE 2
Air capacity correction factors (Multipliers)
INLET
PRESSURES
80°F
psig
kgf/cm
2
27°C
50
3.5
1.35
80
5.6
1.50
100
7.0
1.55
125
8.8
1.63
150
10.5
1.70
175
12.3
1.75
200
14.0
1.80
COOLING MEDIUM*
AMBIENT
750
TEMPERATURE
MULTIPLIER
750
°F
°C
625
80
27
90
32
100
38
110
43
*Air-cooled models; water-cooled models use 1.15 multiplier if cooling
water is below 35°C, 95°F.
INLET COMPRESSED AIR CONDITIONS
INLET TEMPERATURES
90°F
100°F
32°C
38°C
1.05
0.84
1.17
0.95
1.23
1.00
1.31
1.07
1.37
1.13
1.42
1.18
1.47
1.22
OUTLET DEWPOINT
DEWPOINT
TEMPERATURE
°F
°C
1.12
38
3
1.06
45
7
1.00
50
10
0.94
110°F
43°C
0.69
0.79
0.82
0.91
0.95
0.99
1.03
MULTIPLIER
1.0
1.2
1.3