Wieland gesis NRG 5+2 Installation Instruction page 2

Tap-off module

Advertisement

Available languages

Available languages

Installation Instruction (translation from original)
gesis
NRG 5+2
®
Tap-off module
• All gesisNRG system components may only be installed, commissioned and maintained by
qualified electricians.
• Personnel who install, program, operate or maintain this device must have read and
understood these instructions.
• The relevant standards, guidelines, regulations and provisions of the respective country
must be observed.
• Protective measures and mechanisms must correspond to applicable regulations.
• Damaged products may neither be installed nor operated.
• In case of a defect, please return the component to Wieland Electric.
• Never use components from third-party manufacturers. No guarantee shall be offered for
damage resulting from a combination with third-party components.
• Please keep these instructions in a safe place for later reference.
• Use only black system components for black flat cables (BASIC+SIGNAL).
• Use only green system components for green flat cables (BASIC SELV).
• No hazardous interchangeability with systems based on IEC 60309, IEC 60320, IEC 60906
and with national connector and socket systems for home use.
• Interchangeability between installation connector systems from different manufacturers is
not automatically prevented by compliance with EN 61535.
• Compatibility with products from other manufacturers cannot be guaranteed.
• Installation connectors do not replace national connector/socket systems for home use.
• Unused connectors must be provided with closures in easily accessible areas.
• If the feed-in module is later shifted on the flat cable, then the contact openings in the
cable must be closed by cable patches!
• Never install or remove while energized.
gesis
The components of the
® system are used to distribute energy and/or data in building
interiors.
1
S cope of delivery (pre-assembled)
0 B 0 B
The supplied components and cables may neither be changed nor modified.
• Baseplate 1x
• Equipped connecting module 1x
• Cover 1x
2
H ole dimension
1 B 1 B
3
A ssembly
2 B 2 B
1.
Use the two mounting holes to attach the optional baseplate to the desired subsurface.
2.
Install the flat cable in a suitable cable-routing system. Note the cable-installation
direction for the output direction of the connector. Insert the flat cable into the coded
base plate so that it lies flush (93.421.5453.0 for green cable, 91.021.5453.0 for black
cable).
3.
Close the connecting module and latch it with a clearly audible click.
4.
Tighten all of the contact screws consecutively (0.5 Nm).
Doc. # BA001090 - 08/2017 (Rev. B)
gesis
®
NRG BASIC+SIGNAL 91.021.5453.0
gesis
®
NRG BASIC SELV
93.421.5453.0
IN FO
C A U TIO N !
W A RN IN G
Wieland Electric GmbH
Brennerstrasse 10-14
Bamberg 96052 Germany
Tel.:
+49 951 9324-0
Fax:
+49 951 9324-198
Internet: www.wieland-electric.com
Email: info@wieland-electric.com
5.
Close the cover and latch it with a clearly audible click.
Caution:
The screws are not all correctly tightened if the cover does not completely close!
6.
Attach plug connector BST14i2 for BASIC SELV and GST15i2 PB for BASIC+SIGNAL
and latch with a clearly audible click.
4
D isassembly
3 B 3 B
1.
Use a tool (screwdriver) to release
the GST15i2 PB interlock and
remove the connector. No tools are
required to release connector BST14i2.
3.
Loosen the contact screws.
5
T echnical data
4 B 4 B
Rated voltage adapter
Rated voltage cable
Rated current
Protection class
Protection type
Tightening moment of
the contact screws
gesisNRG
5+2
2.
Use a screwdriver to press the interlock lugs
in the direction of the arrow and open the
cover.
4.
Use a tool (screwdriver) to release the base
plate interlock and loosen the module from
the flat cable. Use cable patches to close any
openings in the insulation.
SELV
+Signal
50 V
250 V
50 V
250 V
3 A
6 A
I
IP20
0.5 Nm