Inverter Setting

Constant No.
Name
n003
Run command
selection
n004
Frequency reference
selection
Perform the following constant setting, whenever necessary, before starting communications
between the Inverter and the MECHATROLINK-I/MECHATROLINK-II master.
To run or stop through the MECHATROLINK communications, set 3 to n003. To set frequency,
set 9 to n004.
For details, refer to the VS-606V7 Series Instruction Manual (TOE-S606-11).
0: Digital Operator
1: Control circuit terminal
2: MEMOBUS communications
3: Communications Option Card (Optional)
0: Digital Operator
1: Frequency reference 1 (n024)
2: Voltage reference (0 to 10V)
3: Current reference (4 to 20 mA)
4: Current reference (0 to 20 mA)
5: Pulse train reference
6: MEMOBUS communications
7: Voltage reference of the Digital Operator circuit terminal (0 to 10V)
8: Current reference of the Digital Operator circuit terminal (4 to 20 mA)
9: Communications Option Card (Optional)
Description
17
5 Inverter Setting
Factory Setting
0
0