EEx d II C T6
EN 50014: 1997 + A1: 1999 + A2: 1999
EN 50018: 2000 + A1: 2002
Detector for explosive gases that can be connected to EUROSONDELCO, SIEMENS CC62P -using interface-, FIDEGAS CA -ATEX Certificated- and
any other system provided with 4-20mA standard input 3 wires. The detector gives 4-20mA output proportional to the gas concentration in the
range of 0 to 100% L.E.L. -Low Explosive Limit- of the calibration gas.
FUNCTIONING
When connecting the power supply and after 15 s approx. warm-up time –stabilisation- the output sign goes from the minimum to the maximum
to finally be stablished in the value corresponding to the existing gas concentration.
INSTALLATION
At 1.5 m over the horizontal points of gas consumption or smoke output avoiding air flows. It is not possible to interconnect detectors in serial
or parallel.
Methane, Hydrogen, Acetylene, Ethylene, Ammonia (Exp)
Butane, Propane, Isopropilic Alcohol, Hexane, Gasoline Octane
TECHNICAL CHARACTERISTICS
Voltage Supply
Consumption
Fault Alarm
Warming time
Type of Sensor
Useful life
Coverage area
Measurement range
Response speed
Working and/or storage temperature
Working and/or storage humidity
Pressure Limits
Dimensions -mm-
Weight -gr-
Protection grade
Code of Explosive Atmosphere
Calibrated with specific target gas to measure from 0 to 100% from L.E.I. (Low Explosive Limit)
Do not expose to SILICONE, TRCHLOROETHYLENE, SULPHUR DIOXIDE or HYDROGEN SULPHIDE,
FIDEGAS S/3-2
Detector for Explosive Gases
GAS
12V / 24V CC
120 mA 12V CC / 65 mA 24V CC
0mA
15 s
Catalítyc -Pellistor-
4 years
2
15 m
From 0 to 100% L.E.L.
T90 < 60 s
From -5 to 50 ºC
From 5 to 90% RH
From 95 to 110 kPa
170 x 110 x 70
950
I.P. 435
EEx d II C T6
otherwise it hill be damaged.
Height of Installation
15 cm from ceiling
15 cm from floor