Installing the ERV wired remote controller
Group control with your ERV wired remote controller
Group control means that you are using one ERV wired remote controller to control two or more ERVs at the
same time .
1. Using one ERV wired remote controller to control three ERVs.
ERV
ERV wired remote
controller
2. Using one ERV wired remote controller to control ERVs connected to other ERV repeaters in
a group.
ERV interface module (MIM-N10)
COM1(F1, F2)
CN4
ERV interface module
(MIM-N10)
CN4
COM1(F1, F2)
ERV
• Regardless of the setting of group address (RMC address), only the ERVs connected to COM2
communication wire are controlled in a group .
Caution
• You can control the maximum of 16 ERVs as a group .
• When ERVs of other ERV repeaters are controlled in a group, address of each ERV must be set
differently .
ERV
COM2(F3, F4)
ERV
ERV wired
controller
COM2(F3, F4)
ENGLISH-10
ERV
COM2(F3, F4)
COM2(F3, F4)
remote

Hide quick links: