Maintenance - GEM LSF Instruction Manual

Limit switch boxes with double sensors; modules with slotted proximity switches

Advertisement

Available languages

Available languages

For LSF limit switch boxes with double sensors
1. Description
Limit switch boxes are used to report and control the position of valves which are operated by pneumatic actuators.
The limit switch boxes are equipped with one inductive double sensor. With the enclosed mounting parts the boxes can be
easily and quickly mounted on actuators or valves.
2. Assembling
Risk of injury
The electric components inside the box carry dangerous voltage.
Moreover there is a risk of bruise by some rotating parts.
→ Do not open the housing while operating!
WARNING!
1. Bring the actuator to a completely "Open" or "Close" position.
→ Close:
Valve is closed, channel position is abreast the actuators longitudinal axis.
→ Open:
Valve is open, channel position towards actuator axis.
2. Equate the modules axis with the actuator.
3. Attach the box with bracket on the actuator or valve and fix it.
4. Adapt the control unit by leading the system cable through the cable gland and wiring the single conductors with the
terminal block.
→ Please note the wiring diagramm in the technical data sheet.
→ The wiring diagramm can also be found in the box.
3. Adjusting switch-points
Ex factory the modules are adjusted as following:
Switch-point close:
Switch-point open:
If readjustment should be necessary proceed as following:
1. Remove the housing cover.
2. Push down the exterior ring of the lower switch cam. Turn it until the lower sensor of the proximity switch is activated by the
metal segment in the switch cam (→ LED of sensor shines).
3. Bring the to actuator to position "Open".
4. Proceed similary with the other switch-point (upper sensor).
4. Connecting solenoid valves
The LSF switch-boxes offer the possibility to additionally connect one solenoid valves on the terminal block. If you want to wire
solenoid valves additionally act on the following plan:
1. Replace the sideways blank plugs by a suitable cable gland M12x1,5.
2. Open screws and remove the housing cover.
3. Remove the cable covering.
4. Lead the system cable through the cable gland and wire it with the terminal block.
→ Please note the wiring diagramm in the technical data sheet.
→ The wiring diagramm can also be found in the box.
5. Refasten cable covering and housing cover.

5. Maintenance

Long time outdoor usage can cause gaskets to become brittle after some time. Safe operation can only be guaranteed with
leak-proof boxes!
→ Seals should be exchanged immediately if they are damaged, or at least after five years.
→ Seals and other parts can be ordered at all times.
Instruction manual
Position Valve/Actuator at 0°
Position Valve/Actuator at 90°
4 / 6