Transport; Installation; General Information; Acoustic Emissions - Dimplex SIH 90TU Installation And Operating Instruction

Brine-to-water heat pump for indoor installation
Hide thumbs Also See for SIH 90TU:

Advertisement

Available languages

Available languages

SIH 90TU
5

Transport

For transportation with a sack or vessel truck, it can be mounted
on the front of the device under the transport protection.
The device can be lifted from the rear or front on even ground
using a lift truck or fork-lift truck for transportation. Transport
protection is not compulsory for this.
45°
ATTENTION!
The heat pump must not be tilted more than 45° (in any
direction).
After transportation, the transport fastening in the device is to
be removed from both sides of the base.
ATTENTION!
Before start-up, the transport fastening must be removed.
To remove the panelling, open the individual covers by un-
screwing the respective turn-lock fasteners and then gently tilt-
ing the covers away from the device. Then lift them up out of
the mountings.
www.gdts.one
45°
Remove/screw in
transport lock
452234.66.73 · FD 9910
6

Installation

6.1 General Information

The brine-to-water heat pump must be installed in a frost-free,
dry room on an even, smooth and horizontal surface. The entire
base of the frame should lie directly on the floor to ensure an
adequate soundproof seal. If this is not the case, additional
sound insulation measures may be necessary.
The heat pump must be installed so that maintenance work can
be carried out without hindrance. This can be ensured by main-
taining a clearance of approx. 1 m in front of the heat pump.
Neither frost nor temperatures higher than 35 °C may occur in
the installation location at any time of the year.

6.2 Acoustic Emissions

The heat pump operates silently due to efficient sound insula-
tion. Internal insulation measures should be carried out to pre-
vent vibrations from being transmitted to the foundation or to
the heating system.
7
Installation

7.1 General

The following connections need to be established on the heat
pump:
Flow and return of the brine (heat source system)
Flow and return of the heating system
Temperature sensor
Voltage supply
English
0,5m
1m
EN-5